Installing A Fan Module - Dell S6010-ON Manual Del Usuario

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Installing a Fan Module

The five fan modules and the power supplies are hot-swappable if you install
a second (redundant) power supply.
NOTE: To run the system, the five fan slots must have operating fan
units. If you do not install a module in each slot, the system shuts down
in one minute.
NOTE: The system supports two airflow direction options. You can only
use a single direction in a chassis.
Normal is airflow from the I/O side to the power supply.
Reversed is airflow from the power supply to the I/O side.
There are environmental factors that could decrease the amount of time
required between fan replacements. Check these environmental factors
regularly. Any unusual environmental circumstance at the site that causes an
increase in temperature and/or particulate matter in the air might affect
performance (for example, new equipment installation).
1.
Remove the fan module from the shipping box.
2.
Use the grab handle to slide the module into the switch fan slot.
Figure 13. Install the Fan Module
CAUTION: DO NOT mix airflow directions. All fans must use the same
airflow direction (I/O to PSU side or PSU to I/O side).
22