Standard Connection Diagram - YASKAWA CIPR-GA50C Serie Instrucciones De Instalación Y Operación

200 v class, three-phase input: 0.1 to 22 kw / 200 v class, single-phase input: 0.1 to 4.0 kw / 400 v class, three-phase input: 0.37 to 30 kw
Ocultar thumbs Ver también para CIPR-GA50C Serie:
Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 124

Standard Connection Diagram

Wire the drive as specified by
WARNING
Sudden Movement Hazard. Set the MFDI parameters before you close control circuit
switches. Incorrect Run/Stop circuit sequence settings can cause serious injury or death from moving equipment.
WARNING
Sudden Movement Hazard. Correctly wire the start/stop and safety circuits before you
energize the drive. If you momentarily close a digital input terminal, it can start a drive that is programmed for 3-
Wire control and cause serious injury or death from moving equipment.
WARNING
Sudden Movement Hazard. When you use a 3-Wire sequence, set A1-03 = 3330 [Initialize
Parameters = 3-Wire Initialization] and make sure that b1-17 = 0 [Run Command at Power Up = Disregard
Existing RUN Command] (default). If you do not correctly set the drive parameters for 3-Wire operation before
you energize the drive, the motor can suddenly rotate in reverse when you energize the drive.
WARNING
Sudden Movement Hazard. Check the I/O signals and the external sequences for the
drive before you set the Application Preset function. When you set the Application Preset function (A1-06 ≠ 0), it
changes the I/O terminal functions for the drive and it can cause equipment to operate unusually. This can cause
serious injury or death.
WARNING
Fire Hazard. Install sufficient branch circuit short circuit protection as specified by
applicable codes and this manual. The drive is suited for circuits that supply not more than 31,000 RMS
symmetrical amperes, 240 Vac maximum (200 V Class), 480 Vac maximum (400 V Class). Incorrect branch
circuit short circuit protection can cause serious injury or death.
NOTICE
When the input voltage is 440 V or higher or the wiring distance is longer than 100 m (328
ft), make sure that the motor insulation voltage is sufficient or use an inverter-duty motor or vector-duty motor with
reinforced insulation. Motor winding and insulation failure can occur.
Note:
Do not connect the AC control circuit ground to the drive enclosure. Failure to obey can cause incorrect control circuit
operation.
YASKAWA TOMPC71061753A YASKAWA AC Drive GA500 Installation and Operation Instruction
Figure
1.2.
WWW.NNC.IR
1 English
19