10
SLC 5/03, SLC 5/04, and SLC 5/05 Modular Processors
3. Unplug the battery connector.
Battery
Red
White
Battery Connector
IMPORTANT
4. Remove the battery from the retaining clips.
5. Insert a new battery into the battery retaining clips.
6. Plug the battery connector into the socket as shown above.
7. Re-insert the module into the SLC 500 chassis.
8. Restore power to the SLC 500 power supply.
9. Close the processor door.
IMPORTANT
Publication 1747-IN009E-MU-P - April 2007
The SLC 5/03, 5/04, and 5/05 processors have a capacitor that provides at least
30 minutes of battery back-up while the battery is disconnected. Data in RAM
is not lost if the battery is replaced within 30 minutes.
See page 13 for information on proper battery handling, storage, and
transporting.