합본 Manual_800_1200AF_4 2014.7.17 5:46 PM 페이지1 위너스3 Installation Instructions UTS800/UTS1200 FRAMES UTS800 TO UTS1200 FRONT MOUNTING TYPE CIRCUIT BREAKERS AND MOLDED CASE SWITCHES DANGER HAZARD OF ELECTRIC SHOCK, BURN OR EXPLOSION 1) This equipment must be installed and serviced only by qualified electrical personnel. 2) Turn off and lock out all power supplying this equipment before working on or inside equipment.
합본 Manual_800_1200AF_4 2014.7.17 5:46 PM 페이지4 위너스3 Installation Instructions 2. Manual Operation Manual Operation of the circuit breaker is controlled by the circuit breaker handle and the PUSH TO TRIP button. The circuit breaker has three positions, two of which are shown on the cover with raised lettering to indicate ON and OFF.
합본 Manual_800_1200AF_4 2014.7.17 5:46 PM 페이지5 위너스3 Installation Instructions UTS800/UTS1200 3. Wire Installation DANGER HAZARD OF FALSE TORQUE INDICATION 1) Do not allow conductor strands to interfere with threads of wire binding screw. 2) When installing cables into a lug body make sure cables do not back out during tightening of the wire binding screw. FAILURE TO FOLLOW THESE INSTRUCTIONS WILL RESULT IN EQUIPMENT DAMAGE.
Página 8
합본 Manual_800_1200AF_4 2014.7.17 5:46 PM 페이지6 위너스3 Installation Instructions Restrain Cable Wrap conductors using 30 ft. (9 m) of 3/8 in. (9.5 mm) sisal rope or equivalent. 1) Begin wrapping conductors (A) 2.5 in. (64 mm) above circuit breaker. Wrap conductors five times, leaving 12 plus “X” ft. (4 + “X”m) of excess rope at the first and (B). Pull rope (C) taut.
합본 Manual_800_1200AF_4 2014.7.17 5:46 PM 페이지7 위너스3 Installation Instructions UTS800/UTS1200 4. Accessory and Control Wiring Installation DANGER HAZARD OF ELECTRIC SHOCK, BURN OR EXPLOSION 1) Turn off all power supplying this equipment before working on or inside equipment. 2) Before removing the auxiliary cover in a circuit breaker, make sure there is no voltage present where work is to be performed and circuit breaker is tripped. FAILURE TO FOLLOW THESE INSTRUCTIONS WILL RESULT IN DEATH OR SEVERE INJURY.
Página 11
합본 Manual_800_1200AF_4 2014.7.17 5:46 PM 페이지9 위너스3 Installation Instructions UTS800/UTS1200 10P CONNECTOR TERMINAL ASS'Y, SHORT ZSI IN CONN., 172501-1, AMP TERMINAL, 172773-1, AMP WIRE ASS’Y 25ea 12P CONNECTOR WIRE ASS’Y OCR types Drawing No. Part Name Functions 76671176310 WIRE ASS’Y AG AC OCR Communication, Digital Output, ZSI, Remote Reset A Type 76671176311...
Página 12
합본 Manual_800_1200AF_4 2014.7.17 5:46 PM 페이지10 위너스3 Installation Instructions Caution : Please don’t - In case of the wiring of Earth Leakage ≥30A place the wires below Drawing No. Part Name the guide line 76671176312 WIRE ASS’Y AE AX PX SX OCR 10P CONNECTOR User wiring E1, E2...
합본 Manual_800_1200AF_4 2014.7.17 5:46 PM 페이지11 위너스3 Installation Instructions UTS800/UTS1200 5. Bus Installation DANGER HAZARD OF ELECTRIC SHOCK, BURN OR EXPLOSION 1) Apply appropriate personal protective equipment and follow safe electrical work practices. 2) This equipment must be installed and serviced only by qualified electrical personnel. 3) Turn off all power supplying this equipment before working on or inside equipment.
합본 Manual_800_1200AF_4 2014.7.17 5:46 PM 페이지12 위너스3 Installation Instructions 6. Circuit Breaker Removal DANGER HAZARD OF ELECTRIC SHOCK, BURN OR EXPLOSION 1) Apply appropriate personal protective equipment and follow safe electrical work practices. 2) This equipment must be installed and serviced only by qualified electrical personnel. 3) Turn off all power supplying this equipment before working on or inside equipment.
Página 15
합본 Manual_800_1200AF_4 2014.7.17 5:46 PM 페이지13 위너스3 Installation Instructions UTS800/UTS1200 1) Solution for Circuit Breaker’s abnormal condition Type Condition Possible Causes Solution Terminal unit � Loose terminal unit tightening screw � Tightening with designated torque Temperature Overheating � Faulty booth bar assemble �...
합본 Manual_800_1200AF_4 2014.7.17 5:46 PM 페이지14 위너스3 Installation Instructions 9. Wiring diagram of Control Circuit This diagram is based on "Opening" of circuit breaker, de-energized and normal condition of Trip relay. Internal/External wiring(by customer) Connector of the control circuit terminal of drawout type Voltage Module Power supply 485+...
합본 Manual_800_1200AF_4 2014.7.17 5:46 PM 페이지15 위너스3 Trip Relay Setting UTS800/UTS1200 Trip units Circuit breaker includes factory-installed internal trip units. Be careful not to interchange trip units in the field. There are various kinds of trip units according to rated current and function as follows. 1.
Página 18
합본 Manual_800_1200AF_4 2014.7.17 5:46 PM 페이지16 위너스3 Trip Relay Setting P, S type Knob information Type of knob Mode Setting step ① Long-time current setting (0.4-0.5-0.6-0.7-0.8-0.9-1.0) × In (0.5-1-2-4-8-12-16-20), sec ② Long-time tripping delay @ 6 Ir ③ Short-time current setting (1.5-2-3-4-5-6-8-10-off)×...
Página 19
합본 Manual_800_1200AF_4 2014.7.17 5:46 PM 페이지17 위너스3 Trip Relay Setting UTS800/UTS1200 2) Key and LED Configuration N type Key / LED A, P, S type Key / LED MCP, MCS type Key / LED LED Information LED type Operational mode ①...
Página 20
합본 Manual_800_1200AF_4 2014.7.17 5:46 PM 페이지18 위너스3 Trip Relay Setting 3) Terminal Configuration LED Information Division Figure FRONT REAR 5 3 1 10 8 6 4 2 TTL TX (OCR side) ZSI OUT (+) RS485 (-) Current signal - R phase Power CT (-), GND ZSI OUT (-) LTD contact TTL RX (OCR side)
합본 Manual_800_1200AF_4 2014.7.17 5:46 PM 페이지19 위너스3 Trip Relay Setting UTS800/UTS1200 2. Trip Relay Setting 1) Protection N type Long time Iu = In× × ... Current setting (A) Ir = Iu× × ... 0.83 0.85 0.88 0.93 0.95 0.98 Time delay (s) tr@(1.5×...
Página 22
합본 Manual_800_1200AF_4 2014.7.17 5:46 PM 페이지20 위너스3 Trip Relay Setting A type Long time Current setting (A) Ir = In× × ... Time delay (s) tr@(1.5× × lr) 12.5 Accuracy: ± ± 15% or below tr@(6.0× × lr) tr@(7.2× × lr) 100ms 0.34 0.69...
Página 23
합본 Manual_800_1200AF_4 2014.7.17 5:46 PM 페이지21 위너스3 Trip Relay Setting UTS800/UTS1200 2) Operation characteristic Long-time delay (L) The function for overload protection which has time delayed N, A type characteristic in inverse ratio to fault current. 1. Standard current setting knob: Ir 1) Setting range in P type and S type: (0.4-0.5-0.6-0.7-0.8-0.9-1.0)×In P, S type 2) Setting range in N type and A type: (0.4 ~1.0)×In...
합본 Manual_800_1200AF_4 2014.7.17 5:46 PM 페이지22 위너스3 Trip Relay Setting 3. Operation of A type Trip Relay 1) Menu Tree CAUTION �Each movement within Menu Tree can be done by using Menu and ESC button. �Use UP(△)/Down(▽) button to move around each setting information under Relay Setting Display. �If not pressing any button for 30seconds after moving to other screens, the screen moves back to Measurement Display and any relevant data will not be saved.
Página 25
합본 Manual_800_1200AF_4 2014.7.17 5:46 PM 페이지23 위너스3 Trip Relay Setting UTS800/UTS1200 4) Measurement Display Measurement display Relay setting Communication Communication Present time Event Firmware display Address setting Speed set display index version Display Button Contents 1. The current of R, S, T, N phase are displayed in rotation at 3 second interval 2.
Página 26
합본 Manual_800_1200AF_4 2014.7.17 5:46 PM 페이지24 위너스3 Trip Relay Setting Display Button Contents If pressing ‘Up cursor’ four times on the Relay setting Display, Instantaneous pick up setting value will be displayed. × × 4 If pressing ‘Up cursor’ five times on the Relay setting Display, the setting value of Ground-fault pickup will be displayed. ×...
Página 27
합본 Manual_800_1200AF_4 2014.7.17 5:46 PM 페이지25 위너스3 Trip Relay Setting UTS800/UTS1200 7) Display of measurement Measurement display Relay setting Communication Communication Present time Event Firmware display Address setting Speed set display index version Display Button Contents If pressing ‘MENU’ button 5 times from Measuring Display, move to Event Index. On the Event Index, The information of ×...
합본 Manual_800_1200AF_4 2014.7.17 5:46 PM 페이지32 위너스3 Trip Relay Setting 5. Risk Analysis 1) Risk Analysis occurrence conditions CAUTION The same phenomenon appears, contact your nearest LSIS sales office. Related Function Error No. Condition for Error occurrence when Rating plug is not attached to OCR.
Página 35
합본 Manual_800_1200AF_4 2014.7.17 5:46 PM 페이지33 위너스3 Trip Relay Setting UTS800/UTS1200 2) Risk Analysis operation CAUTION The same phenomenon appears, contact your nearest LSIS sales office. Error Display of LCD Error LED Display Playing Remark Alarm Er-1 PhraseDisplayed Sign : LED Alarm blinks as below 100%- Operation : 1 time blinks →...
Página 36
합본 Manual_800_1200AF_S_6 2014.7.17 5:47 PM 페이지34 위너스3 TABLA DE CONTENIDO Instrucciones de Instalación 1. INSTALACION DEL INTERRUPTOR AUTOMATICO 2. Operación manual 3. Instalación de Cable 4. Instalación de accesorios y cable de control 5. Instalación de barras 6. Desmonte de interruptor 7.
EL INCUMPLIMIENTO DE ESTA INSTRUCCION PODRA CAUSAR LA MUERTE O LESIONES SERIAS. LSIS no es responsable por el mal uso o mala instalación de sus productos. Se advierte al usuario de seguir las recomendaciones, advertencias y peligros relacionados a la seguridad del personal y los equipos tanto como las leyes, códigos y procedimientos generales y locales de seguridad y salud.
Página 38
합본 Manual_800_1200AF_S_6 2014.7.17 5:48 PM 페이지36 위너스3 Instrucciones de Instalación #10-24 UNC-2A TAP(4HOLE) 2.6 [67] 7.9 [200] 7.8 [199] <Fig. 2> Plan de perforación de tornillo de montaje del interruptor <Fig. 3> Dimensiones del escudo del interruptor Dimensiones de los interruptores automáticos - Dimensiones 2.76 [70] 2.76 [70] 4.56 [115.7]...
합본 Manual_800_1200AF_S_6 2014.7.17 5:48 PM 페이지38 위너스3 Instrucciones de Instalación 2. Operación manual La operación manual del interruptor es controlada por la palanca y el botón de disparo. El interruptor tiene tres posiciones, dos de las cuales se indican con letras en relieve para ON y OFF.
합본 Manual_800_1200AF_S_6 2014.7.17 5:48 PM 페이지39 위너스3 Instrucciones de Instalación UTS800/UTS1200 3. Instalación de Cable PELIGRO INDICACION DE RIESGO POR FALLAS DE APRIETE 1) No permita que los hilos del conductor interfieran con las roscas del tornillo de sujeción de cables. 2) Al instalar dos cables en el cuerpo de las zapatas, asegúrese que los cables no se suelten durante el ajuste de apriete del tornillo de sujeción de cables.
Página 42
합본 Manual_800_1200AF_S_6 2014.7.17 5:48 PM 페이지40 위너스3 Instrucciones de Instalación Restrain Cable Enrede los conductores con 9 m (30 pies) de cuerda de sisal de 9,5 mm (3/8 pulg) o equivalente. 1) Comience a enredar los conductores (A) 64 mm (2,5 pulg) por encima del interruptor automático. Enrede los conductores cinco veces, dejando 4 + “X” m (12 + “X” pies) de cuerda en el primer extremo (B).
합본 Manual_800_1200AF_S_6 2014.7.17 5:48 PM 페이지41 위너스3 Instrucciones de Instalación UTS800/UTS1200 4. Instalación de accesorios y cable de control PELIGRO PELIGRO DE DESCARGA ELECTRICA, QUEMADURA O EXPLOSION 1) Desenergice el equipo antes de realizar cualquier trabajo en él. 2) Antes de montar el interruptor al sistema eléctrico, asegúrese que no exista tensión presente en donde se realizará el trabajo. EL INCUMPLIMIENTO DE ESTA INSTRUCCION PODRA CAUSAR LA MUERTE O LESIONES SERIAS 1) Retire la cubierta auxiliar y la cubierta de seguridad(A).
Página 45
합본 Manual_800_1200AF_S_6 2014.7.17 5:48 PM 페이지43 위너스3 Instrucciones de Instalación UTS800/UTS1200 10P Conector TERMINAL ASS'Y, SHORT ZSI IN CONN., 172501-1, AMP TERMINAL, 172773-1, AMP Montaje de cable 25ea 12P Conector WIRE ASS’Y OCR types Drawing No. Part Name Functions 76671176310 WIRE ASS’Y AG AC OCR Comunicación, salida digital, reset remoto Tipo A...
Página 46
합본 Manual_800_1200AF_S_6 2014.7.17 5:48 PM 페이지44 위너스3 Instrucciones de Instalación - Cuando se cablea en fuga a tierra ≥30A Atención : No ponga los cables debajo de No. de dibujo Nombre del parte línea de guía 76671176312 WIRE ASS’Y AE AX PX SX OCR 10P Conector Cableado usuario...
합본 Manual_800_1200AF_S_6 2014.7.17 5:48 PM 페이지45 위너스3 Instrucciones de Instalación UTS800/UTS1200 5. Instalación de barras PELIGRO PELIGRO DE DESCARGA ELECTRICA, QUEMADURA O EXPLOSION 1) Utilice equipo de protección personal apropiado y siga las prácticas de seguridad para trabajos eléctricos. 2) Solamente el personal especializado en electricidad deberá instalar y prestar servicio de mantenimiento a este equipo. 3) Desenergice el equipo antes de realizar cualquier trabajo en él.
합본 Manual_800_1200AF_S_6 2014.7.17 5:48 PM 페이지46 위너스3 Instrucciones de Instalación 6. Desmonte de interruptor PELIGRO PELIGRO DE DESCARGA ELECTRICA, QUEMADURA O EXPLOSION 1) Utilice equipo de protección personal apropiado y siga las prácticas de seguridad para trabajos eléctricos. 2) Solamente el personal especializado en electricidad deberá instalar y prestar servicio de mantenimiento a este equipo. 3) Desenergice el equipo antes de realizar cualquier trabajo en él.
Página 49
합본 Manual_800_1200AF_S_6 2014.7.17 5:48 PM 페이지47 위너스3 Instrucciones de Instalación UTS800/UTS1200 1) Solución para condiciones anormales del interruptor Tipo Condición Causas posibles Solución Sobrecalentamiento de � Tornillo de apriete de unidad de terminal flojo � Ajustar de acuerdo al par de torsión designado Incremento de unidad de terminal �...
합본 Manual_800_1200AF_S_6 2014.7.17 5:48 PM 페이지48 위너스3 Instrucciones de Instalación 9. Diagrama de cableado de circuito de control Este diagrama está basado en "apertura" del interruptor, de-energizado y en condición normal de relé de disparo. Power supply 485+ AXb AX 485- UVT SHT Símbolo y descripciones...
합본 Manual_800_1200AF_S_6 2014.7.17 5:48 PM 페이지49 위너스3 Ajuste de relé de disparo UTS800/UTS1200 Unidades de disparo El interruptor incluye unidades de disparo interno desde la fábrica. Hay varios tipos de unidades de disparo de acuerdo a la corriente nominal y funciones como siguiente. 1.
Página 52
합본 Manual_800_1200AF_S_6 2014.7.17 5:48 PM 페이지50 위너스3 Ajuste de relé de disparo Información de botón tipo P y S Tipo de botón Modo Ajustes ① Ajuste de corriente de largo tiempo (0.4-0.5-0.6-0.7-0.8-0.9-1.0) × In (0.5-1-2-4-8-12-16-20), sec ② Retraso de disparo de largo tiempo @ 6 Ir ③...
Página 53
합본 Manual_800_1200AF_S_6 2014.7.17 5:48 PM 페이지51 위너스3 Ajuste de relé de disparo UTS800/UTS1200 2) Clave y configuración de LED Clave / LED de tipo N Clave / LED de tipo A, P y S Clave / LED de tipo MCP y MCS Información de LED Tipo de LED Modo de operación...
Página 54
합본 Manual_800_1200AF_S_6 2014.7.17 5:48 PM 페이지52 위너스3 Ajuste de relé de disparo 3) Configuración del terminal Información de LED División Figura FRONTAL ATRAS ARRIBA 5 3 1 10 8 6 4 2 TTL TX (OCR side) ZSI OUT (+) RS485 (-) Signo de corriente - fase R Power CT (-), GND ZSI OUT (-) Contacto LTD...
합본 Manual_800_1200AF_S_6 2014.7.17 5:48 PM 페이지53 위너스3 Ajuste de relé de disparo UTS800/UTS1200 2. Ajuste de relé de disparo 1) Protección Tipo N Largo tiempo Iu = In× × ... Ajuste de corriente (A) Ir = Iu× × ... 0.83 0.85 0.88 0.93...
Página 56
합본 Manual_800_1200AF_S_6 2014.7.17 5:48 PM 페이지54 위너스3 Ajuste de relé de disparo Tipo A Largo tiempo Ajuste de corriente (A) Ir = In× × ... Tiempo de retraso (s) tr@(1.5× × lr) 12.5 Precisión: ± ± 15% menos tr@(6.0× × lr) tr@(7.2×...
Página 57
합본 Manual_800_1200AF_S_6 2014.7.17 5:48 PM 페이지55 위너스3 Ajuste de relé de disparo UTS800/UTS1200 2) Caracteristicas de operacion Retraso de largo tiempo (L) La función para protección de sobrecarga que posee características de retraso de tiempo ln Tipo N y A inversamente proporcional a la corriente de falla.
합본 Manual_800_1200AF_S_6 2014.7.17 5:48 PM 페이지56 위너스3 Ajuste de relé de disparo 3. Operation of A type Trip Relay 1) Árbol de menú ATENCIÓN �Cada movimiento dentro del árbol de menú se puede hacer usando botón de Menu y ESC. �Use los botones UP(△)/Down(▽) para mover entre cada información de ajuste bajo Relay Setting Display.
Página 59
합본 Manual_800_1200AF_S_6 2014.7.17 5:48 PM 페이지57 위너스3 Ajuste de relé de disparo UTS800/UTS1200 4) Pantalla de medición Pantalla de medición Relay setting Communication Communication Present time Event Firmware display Address setting Speed set display index version Pantalla Botón Contenido 1. La corriente de las fases R, S, T y N se muestran en rotación con un interval de 3 segundos 2.
Página 60
합본 Manual_800_1200AF_S_6 2014.7.17 5:48 PM 페이지58 위너스3 Ajuste de relé de disparo Pantalla Botón Contenido Presionando el cursor Up cuatro veces en la patalla de ajuste de relé, se mostrará el valor de ajuste de arranque instantáneo. × × 4 Presionando el cursor Up cinco veces en la patalla de ajuste de relé, se mostrará...
Página 61
합본 Manual_800_1200AF_S_6 2014.7.17 5:48 PM 페이지59 위너스3 Ajuste de relé de disparo UTS800/UTS1200 7) Pantalla de medición Pantalla de medición Relay setting Communication Communication Present time Event Firmware display Address setting Speed set display index version Pantalla Botón Contenido Presionando el botón de 'MENU' cinco veces en la patalla de medición, se cambiará a la patalla de Event Index. La ×...
합본 Manual_800_1200AF_S_6 2014.7.17 5:48 PM 페이지60 위너스3 Ajuste de relé de disparo 4. Curva de características de relé de disparo 1) Retraso de largo tiempo 5000 2000 Ir=0.4~1xIn 1000 0.05 0.02 0.01 - 60 -...
Página 63
합본 Manual_800_1200AF_S_6 2014.7.17 5:48 PM 페이지61 위너스3 Ajuste de relé de disparo UTS800/UTS1200 2) Retraso de corto tiempo 5000 2000 1000 0.05 0.05 0.02 0.01 - 61 -...
Página 64
합본 Manual_800_1200AF_S_6 2014.7.17 5:48 PM 페이지62 위너스3 Ajuste de relé de disparo 3) Instantáneo / Falla a tierra Ig=0.2~1xIn Ii=2~12xIn 3x 4x 6x 8x10x 12x 15x I2t OFF 0.05 0.05 0.02 0.01 - 62 -...
Ajuste de relé de disparo 5. Análisis de riesgo 1) Condiciones de ocurrencia de análisis de riesgo ATENCIÓN Si el mismo problema ocurre, contacte a la oficina de ventas LSIS más cercana. Función asociado No. de error Condiciones para que ocurra el error El módulo calibre relé...
Página 69
합본 Manual_800_1200AF_S_6 2014.7.17 5:48 PM 페이지67 위너스3 Ajuste de relé de disparo UTS800/UTS1200 2) Operación de análisis de riesgo ATENCIÓN Si el mismo problema ocurre, contacte a la oficina de ventas LSIS más cercana. Error Pantalla de error en LCD Pantalla de error en LCD Transmisión...
Página 70
�LSIS Gurgaon Office � � Gurgaon, India continuous product development and improvement. Address: 109 First Floor, Park Central, Sector-30, Gurgaon- 122 002, Haryana, India e-mail: hwyim@lsis.biz 2014. 01 Susol UL Manual_UTS 800/1200 (E) 2014. 01/(01) 2014. 01 Printed in Korea STAFF / Imprimido en Corea...