합본 Manual_800_1200AF_4 2014.7.17 5:46 PM 페이지9 위너스3
CONN., 172501-1, AMP
1ea
WIRE ASS'Y OCR types
No.
Drawing No.
1
76671176310
2
76671176311
WIRE ASS'Y A ZK PS CKA OCR
3
76671176312
WIRE ASS'Y AE AX PX SX OCR
<Fig.15 > Components of wire ass'y OCR and types
02
01
04
03
06
05
08
07
10
09
12
11
14
13
16
15
18
17
20
19
Caution
TRIP or OFF STATE
Installation Instructions
TERMINAL ASS'Y, SHORT ZSI IN
1ea
TERMINAL, 172773-1, AMP
25ea
Part Name
WIRE ASS'Y AG AC OCR
Communication, Digital Output, ZSI, Remote Reset
Communication, Digital Output, ZSI, Remote Reset, Earth Leakage(<30A), Voltage Module
Communication, Digital Output, ZSI, Remote Reset, Earth Leakage(>30A), Voltage Module
6x13.3 lb-in
(6x1.5N·m)
<Fig.16 > Disassembling cover and short connector
WIRE ASS'Y
1ea
Functions
<Table.4> Terminal Number and Description
Number
Marking
01
485+
02
485-
03
R1
04
R2
05
524
06
534
07
544
08
513
09
Z3
10
Z4
11
Z1
12
Z2
13
R11
14
R22
15
E1 or B1
16
E2 or B2
17
V1
18
V2
19
V3
20
VN
In case of not using ZSI function
CONN.,172501-1,AMP
Caution
: If not using ZSI function of Trip Relay (OCR), please short ZSI
INPUT of terminal No.11,12 (ZSI IN +, ZSI IN-) by using the
"TERMINAL ASS'Y,SHORT ZSI IN"
- 9 -
UTS800/UTS1200
10P CONNECTOR
12P CONNECTOR
OCR
A Type
P, S Type
P, S Type
Description
Comm. +
Comm. -
Power +
Power -
Relay Output (Long time)
Relay Output (Short time/Instantaneous)
Relay Output (Ground fault/PAL)
Relay Output Common
ZSI Out +
ZSI Out -
ZSI In +
ZSI In -
Remote Reset +
Remote Reset -
Earth Leakage +
Earth Leakage -
VR Input
VS Input
VT Input
V Input Common
TERMINAL ASS'Y, SHORT ZSI IN
No. 11, 12 SHORTED