After heater has been properly mounted
to the building structure and appropriate
branch circuit wiring has been routed to
the heater location in accordance with the
National Electrical Code and local codes,
the heater is now ready for the heater to
be connected to the branch circuit.
Risk of Electric Shock or Fire
Make sure electric power is disconnected
at main electrical panel before attempting
to connect heater to branch circuit. Verify
branch circuit voltage is same as noted on
heater nameplate. Connecting heater to a
voltage greater than the heater
nameplate rating could damage the
heater and cause a fire.
WIRING INSTRUCTIONS
Heater is provided with a 28.3mm hole into wiring
compartment for routing of branch circuit conductors.
Appropriate conduit and fittings must be provided for
correct and safe installation.
1. Remove the field wiring cover located on bottom of
heater by removing two screws. See Figure 8 and Figure 9
for reference.
2. Bring branch circuit conductors to heater and into
hardwire according to right position. Install appropriate
cable fitting into the heater as shown in Figure 10 and
Figure 11.
3. Following the wiring diagrams in Figure 12 connect the
supply wiring to the heater lead wires inside the wiring
compartment.
• Green pigtail – connect to earth ground
• Black pigtails – connect to branch circuit power
4. Replace wiring box cover with two screws previously
removed.
5. Adjust louvers to desired position; louvers are
designed so that they cannot be completely closed. Do
not attempt to defeat this safety feature.