TSSD1CO
167391
TSQD1CO
167390
Analogue time switch 24 h
Analog-Zeitschaltuhr 24 h
Minuterie analogique 24 h
Interruttore orario analogico 24 h
Interruptor horario analógico 24 h
Interruptor horário analógico 24 h
Analoge schakelklok 24 h
Analogowy zegar sterujący 24 h
GB
D
F
I
E
P
NL PL
ENGLISH
Basic safety instructions
WARNING
Danger of death through electric shock or fire!
Installation should only be carried out by a qualified electrician!
Designated use
• The time switch can be used for lighting, ventilation, fountains,
advertising hoardings etc.
• Only for use in closed, dry rooms
• Installation on DIN top hat rail (in accordance with DIN EN 60715)
Disposal
Dispose of device in environmentally sound manner
Description
Connection/installation
WARNING
Warning, danger of death through electric
shock!
Must be installed by qualified electrician!
Disconnect power source!
Cover or shield any adjacent live components.
Ensure device cannot be switched on!
Check power supply is connected!
Earth and bypass!
for TSQD1CO only
Quarz movement only starts in a few minutes
after power is switched on.
Full power reserve is achieved after approx.
5 days.
TSQD1CO
1810822
R200h (230V)
110–230V~
–20T
R100h (110V)
50–60Hz
16(4) 250
~
1
2
3
TSQD1CO
Switching pre-selection/manual
setting
Program timing disc
Switching segments (1 = 15 mins)
Morning/afternoon
(AM/PM) time display
Hand for setting time (hours and
minutes) can be adjusted anti-
clockwise and clockwise; turn
minute hand firmly to left
Three way switch:
Permanent ON – AUTO –
Permanent OFF
Klick
45°
45°
Service address/Hotline
Eaton Industries (Austria) GmbH
Scheydgasse 42
A-1215 Wien
www.eaton.com
N
L1
L1/L2/L3
Set time
e.g. 3:00 (morning)
e.g. 15:00 (afternoon)
Set manual operation/
switching pre-selection
in advance 3:00 ON (= 1)
= 1
n
The time switch operates the set swit-
ching times, i.e. it returns to program.
Connection, technical data see on the back side
Technical Data
TSSD1CO
Operating voltage:
230 V~, +10 %/-15 % 50 Hz
Power consumption:
max. 1 VA
Switching contact:
floating (not for SELV/PELV)
Contact:
two-way switch
Gap:
<3 mm (µ)
Contact material:
Ag
Switching capacity:
16 A, 250 V~, cos ϕ = 1
4 A, 250 V~, cos ϕ = 0,6
Incandescent lamp load: 1100 W
Fluorescent lamp load: parallel-corrected
2 x 40 W (4,7µF)
Perm. ambient temperature: –20 °C ... +55 °C
Protection class:
II in acc. with EN 60730-1 for
designated installation
Protection rating:
IP 20 in accordance with EN 60529
Time accuracy:
synchronised with mains
Power reserve:
– –
Pollution degree:
2
Type:
1 BRTU
309517
Set switching times
e.g. 6:15–10:45; 16:15–21:00 ON
21:00
6:15
16:15
10:45
Set 1 –
– 0 permanent
n
switching
1
Program is not operated.
1 = Permanent ON
0 = Permanent OFF
TSQD1CO
110–230 V~, 50–60 Hz
max. 1 VA
floating (not for SELV/PELV)
two-way switch
<3 mm (µ)
Ag
16 A, 250 V~, cos ϕ = 1
4 A, 250 V~, cos ϕ = 0,6
1100 W
parallel-corrected
2 x 40 W (4,7µF)
–20 °C ... +55 °C
II in acc. with EN 60730-1 for
designated installation
IP 20 in acc. with EN 60529
≤ ±1 s/s day at +20 °C
R 200 h (230 V), R 100 h (110 V)
2
1 BSTU