Fault Codes, cont'd.
Temperature Monitor Control (TMC) - Red Light Flashing
FAST
On/Off 2 to 3 times per
second
The TMC has sensed an open
circuit in the thermocouple circuit
Is thermocouple
plugged into T/C
connector of TMC?
No
Plug in thermocouple.
Once plugged in, TMC
will self-recover and
oP LI fault code will be
cleared.
2118, 2118IM, 2118IMD Series
A
From Previous Page
Is red light
FAST
flashing FAST or
SLOW?
Replace thermocouple
Yes
20
SLOW
SLOW
On/Off once per second
The TMC has sensed the input
voltage to be below 9.5 VDC
Make sure input voltage
to TMC +12V terminal is
between 10.5 –15.4 VDC.
Once input voltage is
above 10.0 VDC, High
Temperature Monitor will
self-recover and oP LI
fault code will be cleared.