en | Wiring and Addressing Information
3.
Insert the detector head into the base.
X
Figure 3.2 Activating the Locking Mechanism
Release the locked detector head by pushing hard through the dimple (O) on the detector's outer rim with a
screwdriver (see Figure 3.3) and at the same time, turning the detector head to the left.
O
Figure 3.3 Releasing the Detector
4

Wiring and Addressing Information

4.1

Wiring Information

WARNING!
Do not twist or loop the wires around the terminals. In and out wires for terminal connection
must be cut, stripped, and inserted as individual ends.
The following wire gauges and maximum line lengths are tested and approved.
2
18 AWG (0.8 mm
) -> 4000 ft (1200m)
2
16 AWG (1.3 mm
) -> 6225 ft (1900m)
2
14 AWG (2.1 mm
) -> 7200 ft (2200m)
2
12 AWG (3.3 mm
) -> 9850 ft (3000m)
Standard non-twisted, non-shielded wiring (plain old wire) for the SLCs is recommended.
NOTICE!
Voltage drop calculations along with anticipated wire distance should be considered to ensure
a voltage supply of at least 24 V at every detector.
F.01U.123.589 | 5.0 | 2012.02