A
Distance from ventilation grid.
B
Distance from ventilation grid.
C
Lateral side of a window.
D
Top of a window.
E
Top of a door.
F
Lateral side of a door.
G
Adjacent wall.
H
Height from adjacent wall.
I
Adjacent building.
4.13. The minimum distance from gas outlet to ground shall be minimum 65cm, depending however on the
surface. Gas may burn grass, plants, trees located near the gas outlet. In the event that the stove outlet is
lower, suitable safety measures should be taken. The outlet pipe should never be below the extractor itself.
4.14. The distance between gas outlet and public pavement shall be minimum 2.20 m. See your local regulations.
4.15. Never fix the gas outlet flex in a chimney or a flex already installed which diameter is 4 times as large as the
stove's flex (Ø100 max. 314 cm
channeled to the top.
If the tube that was installed previously was used with another type of heating (wood, oil, etc.), you MUST
clean it thoroughly, to reduce the risk of fire in the gas vent.
4.16. Gas outlet flex cannot be installed in a share pipe such as the pipe of an extractor hood, another stove or
heating system.
4.17. If gas outlet installation is wrong, combustion air's homogeneity might be bad which could make the wall of
the house or the building dirty, aggregate trash inside the stove and thus be the source of premature
degradation of the spare parts and gas outlet pipe.
4.18. The air input pipe should not be drained with the risk of affecting the correct operation of the stove. For this
reason, and in order to facilitate fresh air input, it is necessary to set up a ventilation grid AT NOT LESS than
50cm both horizontally and vertically from gas output, see point 4.12.
Direct air currents shall also be avoided as they might prevent a correct operation of the stove and as a
consequence, heat performance.
4.19. In any case the design of the chimney termination will impede the free diffusion in the atmosphere of
combustion products. A metallic mesh with a gap of 3x3 cm can be placed to avoid the entry of birds or
unwanted objects.
COMPLIANCE WITH THESE NORMS ARE OUT OF ECOFOREST'S CONTROL; ECOFOREST DOES NOT BEAR THE
RESPONSIBILITY FOR ANY RESULTING DAMAGE.
WE RECOMMEND THAT A CONFIRMED SPECIALIST SETS UP YOUR PELLETS STOVE.
4.20. Check the space between the stove, the fuel, and any flammable material, check drawing 5 and 6.
4.21. Do not install the stove in a sleeping room.
4.22. The power cable provided by ECOFOREST is 1.4m long; you might need a longer one. Always use a cable with
ground plug.
FREE SPACES AND MINIMUM DISTANCES WITH FLAMMABLE MATERIAL.
Security distances should be respected when the stove is installed in spaces where materials, either
construction materials or those surrounding the stove, are likely to be flammable.
4.22. If the floor is made of a combustible material, install a fire protection between the floor and the stove.
500 mm
500 mm
1250 mm
650 mm
650 mm
1250 mm
300 mm
2300 mm
650 mm
2
). When installing the stove in higher section the gas outlet must be
LOCATION AND SAFETY DISTANCES.
28
Drawing 4