Flygt's monitoring unit, 83 58 40, is designed for use in
pumps from model 3231 and larger models equipped
with drive units 680-945. Turbines equipped with
generators 705-935 are also covered by the monitoring
system.
The monitoring unit is connected to the standardized
range of sensors incorporated in all the products
covered.
Channel A, liquid level
This channel is used, for example, for monitoring of
possible liquid leakage into the stator casing. A sensor
is incorporated in the lower part of the stator casing.
The sensor changes resistance from about
1.5 kΩ to about 330 Ω if liquid enters.
Another sensor that can be connected to this channel
is the water in oil sensor, called CLS (capacitive
leakage sensor). The CLS-30 monitors the content of
water in the oil housing or the gear box and alarms at
a percentage > 35.

GENERAL

These instructions do not apply to units delivered
with article number 83 58 41, which are programmed
for other functions. The fault tracing scheme applies
to the standard version 83 58 40 only.
The figures in the text refer to the numbers on the
front cover (1 – 32) and also to the picture below
(51 – 61).

FUNCTIONS

Input indication
The pilot lamp 51 is lit to indicate interruption or short-
circuit.
Alarm
After alarm for about 5 seconds, the alarm function A
is activated, the red pilot lamp 53 is lit, the
function is activated (the pilot lamp is lit) and the
interlock (11 – 12) drops, whereby the pump/turbine is
disconnected and the pilot lamp 59 will go out.
Reset
Resetting can only be done manually, by pushing the
reset button connected to the entrance (22, 23).