2. INDOOR UNIT INSTALLATION
2.5 INSTALL THE PANEL
CAUTION
Before installation of the panel, be sure to remove the cushion for transportation between the fan and
orifice.
Install the panel according to below instructure after piping and wiring work has completed.
Joint the connecting sections of panel, ceiling surface and indoor unit closely. Any gap between them will
cause air leakage and this generate condensation or water leakage.
2.5.1 Push the two grille switches simultaneously, then lift the grille up and remove the air inlet grille.
Take out the installation covers from 4 corners.
Grille switch
2.5.2 Install the panel
Align corner marked with the piping side and drain side with piping interface and drainage interface of the main body.
Hang the panel to the hooks on the main body.
Tighten the screw evenly under the panel hook until the thickness of sponge between the main body and panel is reduced to
about 4~6mm, and the edge of panel should contack the ceiling well.
Connect the wire of swing motor to the corresponding splice on main body.
2.5.3 Install the air inlet grille
Hang the hook behind the air inlet grille on to the panel.
Connect the wire of display to the corresponding plug on main body.
Close the air inlet grille.
Press the installation cover gently into the panel.
Piping port
Drain port
Screw
Cross-screwdriver
Hook panel
Installation
cover's rope
Tap Screw
Slide the four sliders
in the corresponding
channel when installing
the cover
GB-9