Simbol
Code
Parameter
c0
Comp., fan and AUX delay on start-up in dead band
c1
Minimum time between successive starts
c2
Minimum compressor OFF time
c3
Minimum compressor ON time
c4
Duty setting
cc
Continuous cycle duration
c6
Alarm bypass after continuous cycle
c7
Maximum pump down time
c8
Comp. start delay after open PD valve (factory set to 0 and not visible)
c9
Enable autostart function in PD
c10
Select Pump down by time or pressure
0: Pump down by pressure
1: Pump down by time
c11
Second compressor delay
Simbol
Code
Parameter
d0
Type of defrost
0: Electric heater defrost by temperature
1: Hot gas defrost by temperature
2: Electric heater defrost by time
3: Hot gas defrost by time
4: Electric heater defrost thermostat by time
dI
Interval between defrosts
dt1
End defrost temperature, evaporator
dt2
End defrost temperature, aux evap.
dP1
Maximum defrost duration, evaporator
dP2
Maximum defrost duration, aux evap.
d3
Defrost start delay
d4
Enable defrost on start-up
0: No defrost is performed when the instrument is switched on
1: A defrost is performed when the instrument is switched on
d5
Defrost delay on start-up
d6
Display on hold during defrost
0: Alternating display of dEF and probe value
1: Display of the last temp. shown
2: Display of dEF steady
dd
Dripping time after defrost
d8
Alarm bypass after defrost
d8d
Alarm bypass after door open
d9
Defrost priority over compressor protectors
0: The protection times c1, c2 and c3 are observed
1: The protection times c1, c2 and c3 are not observed
d/1
Display of defrost probe 1
d/2
Display of defrost probe 2
dC
Time base for defrost
0: dI in hours, dP1 and dP2 in minutes
1: dI in minutes, dP1 and dP2 in seconds
d10
Compressor running time
d11
Running time temperature threshold
d12
Advanced defrost
dn
Nominal defrost duration
dH
Proportional factor, variation in dI
Simbol
Code
Parameter
A0
Alarm and fan differential
A1
Type of threshold 'AL' and 'AH'
0: AL and AH are relative thresholds
1: AL and AH are absolute thresholds
AL
Low temperature alarm threshold
AH
High temperature alarm threshold
Ad
Low and high temperature signal delay
A4
Digital input 1 confi guration
0: Input not active
1: Immediate external alarm
2: Delayed external alarm
3: If model M, probe selection
3: Other models enable defrost
4: Start defrost
5: Door switch with compressor and fan stop
6: Remote on/off
7: Curtain switch
AD
U.O.M.
AD
min
AD
min
AD
min
AD
min
AD
min
AD
ore
AD
ore
AD
s
AD
s
AD
fl ag
AD
fl ag
AD
s
AD
U.O.M.
AD
fl ag
AD
ore
AD
°C/°F
AD
°C/°F
AD
min
AD
min
AD
Min
AD
fl ag
AD
min
AD
-
AD
min
AD
ore
AD
ore/min C
AD
fl ag
AD
°C/°F
AD
°C/°F
AD
fl ag
AD
ore
AD
°C/°F
AD
-
AD
-
AD
-
AD
U.O.M.
AD
°C/°F
AD
fl ag
AD
°C/°F
AD
°C/°F
AD
min
A
-
D
-
8
Type
Min
Max
Def.
C
0
15
0
C
0
15
0
C
0
15
0
C
0
15
0
C
0
100
0
C
0
15
0
C
0
250
2
C
0
900
0
C
0
60
5
C
0
1
0
C
0
1
0
C
0
250
4
Type
Min
Max
Def.
C
0
4
0
F
0
250
8
F
-50
200
4.0
F
-50
200
4.0
F
1
250
30
F
1
250
30
C
0
250
0
C
0
1
0
C
0
250
0
C
0
2
1
F
0
15
2
F
0
15
1
0
250
0
C
0
1
0
F
-
-
-
F
-
-
-
C
0
1
0
C
0
250
0
C
-20
20
1.0
C
0
3
0
C
1
100
65
C
0
100
50
Type
Min
Max
Def.
C
0.1
20
2.0
C
0
1
0
F
-50
200
0.0
F
-50
200
0.0
F
0
250
120
C
0
14
0
C
0
14
3
+050004105 rel. 2.2 del 26.09.07