3. Installation respective retro -
fitting of the PDC to a meter
The ZENNER PDC modules are designed primar-
ily for all water meters of ZENNER which can be
retrofitted with a pulse generator (model -N). Basi-
cally, a PDC can be connected to any meter with
suitable pulse output.
3.1. Connection (retrofitting) of PDC IP68
with open cable end to meter with existing
pulse output
Connect the pulse output of the meter with the
PDC-cable. Use a cable connector and possibly
observe the correct polarity.
Reed contact
pulse
Open collector
3.2. Connection (retrofitting) PDC IP54 with
pulse output of any meter
Connect pulse output cable from the meter to
the corresponding terminals on the PDC circuit
board.
-
+
INPUT A
GND
S 1
INPUT B
S 2
GND
white
Pulse Input
brown (GND)
No push-pull drive!
Only for npn or n channel!
white
Min pulse width: 20 ms
Max pulse frequency: 25 Hz
brown (GND)
Fig.:
Connection sketch
+
PDC
+
3.3. Mounting (retrofit) PDC with ex-works
installed ZENNER pulser to corresponding
ZR-water meters
Please refer to the relevant installation instruc-
tions of the pulser and take the PDC as de-
scribed in section 3.4 in operation.
3.4. Commissioning PDC
The commissioning is performed via the optical
interface.
The parameters to be programmed using a laptop
with the Global ZENNER meters Manager (GMM)
software (Configuration Manager license), the
universal interface MinoConnectRadio with Blue-
tooth interface and the associated special ZEN-
NER infrared optical head IrCombiHead. Alter-
natively, the use of an Android handhelds with a
MeterReaderLight license instead of a laptop is
possible.
Configure at least:
serial number of meter connected to the PDC
module
Initial value = present value of the register of the
connected meter
Pulse value of the connected meter
The respective transmission interval is preset.
Additional setting parameters:
Reset logger values
Reset status bits (manipulation, error)
AES-key (depending on the software license)
Activation takes place automatically when the
PDC module has received more than 10 pulses
from the meter.