Kenmore trio 596.76502500 Guía De Uso Y Cuidado página 30

Refrigerador con congelador inferior
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Refrigerator
is
leaking water
ice forms in inlet
tube to ice maker
Water flow is
slower than normal
, Piasdc tubing was used to compbte
water connection.
° Improper saddb vaive was installed.
, Water pressure
is too How.
, Freezer temperature
is too high.
, Water pressure
is too How.
, Improper saddb vaive was installed.
, Copper tubing has kinks.
The manufacturer recommends using copper tubing
for installation. PUasticis less durable and can cause
leakage. Sears is not responsible
for property
damage due to improper
installation
or water
connection.
Check water connection procedure (see page 13:}.
Seif-pbrdng
and %_"saddb vaives cause Howwater
pressure and may dog the iine over time. Sears is
not responsible
for property damage due to
improper installation or water connection.
Water pressure must be between
35 to 100 pounds
per square inch (psi:} to function
properly. A
minimum
pressure
of 35 psi is recommended
for
refrigerators
with water filters.
Adjust freezer control (see page 15}. Freezer is
recommended to be approximately 0° F (-18° C}.
Water pressure must be between 35 to 100 psi to
function properly. A minimum pressure of 35 psi is
recommended for refrigerators with water filters.
Check water connection procedure in your
Installation Instructions. Self-piercing and %/'
saddle valves cause low water pressure and may
clog the line over time. Sears is not responsible
for property damage dae to improper
installation
or water connection.
Open water
valve completely and check for leaks.
Turn off water supply and remove kinks. If kinks
cannot be removed, replace tubing.
3O