2. Verify that the sensor is mounted at least six feet (2 meters) away from any heating/ventilating/air conditioning device that may
cause false detection. Verify that there is no significant heat source (such as a high wattage light bulb) mounted near the sensor.
3. If the lights still do not turn OFF, call 800.879.8585 for technical support.
Sensing motion outside desired areas
1. Select PIR Sensitivity – Low (DIP switch 5 = ON) if necessary.
2. Mask the PIR sensor's lens to eliminate unwanted coverage area.
3. Adjust the Ultrasonic Sensitivity. Rotate the trimpot conterclockwise to reduce sensitivity.
Red LED is OFF all the time and the sensor features don't work.
1. Check the Ultrasonic trimpot. If it is set at fully counter-clockwise (MIN) the unit is in Service Mode. Set the trimpot to a mid-range
position.
2. If resetting the Time Delay switches does not set the sensor features, call technical support.
Wattstopper DSW series wall switches fit behind industry standard decorator-style switch cover plates. Cover plates are not included.
Units come in the following colors, which are indicated by the final suffix of the catalog number (shown here in parentheses):
White (-W), Light Almond (-LA), Ivory (-I), Grey (-G), Black (-B).

COVER PLATES