Routine Maintenance - GLOBEAIRE RDD Manual De Instalación, Operación Y Mantenimiento

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

8.
For RDB models: Belt tension can be adjusted by
loosening four fasteners on the drive frame, see
Figure 11. The motor
plate slides on the
slotted adjusting arms
and drive frame angles
in the same manner.
Four (4) fasetners in
total.
Identifical fasteners on
opposing side must also be loosened.
9a. Sizes 071-161: Belts should be tensioned just
enough to prevent slippage at full load.
Note: Belts should have a slight bow on the slack
side while running at full load (see Figure 12a).
Slack
Side
Figure 12a
Sizes 180-540: Belt tension should be adjusted to
allow 1/64 in. (0.397 mm) of deflection per inch of
belt span. For example, a 15 in. (381 mm) belt span
should have 15/64 in. (0/234 mm) (or about 1/4 in.
(6 mm)) of deflection with moderate thumb pressure
at mid-point between pulleys, see figure 12 b.
10. The adjustable motor pulley is factory set for the
RPM specified. Speed can be increased by closing
or decreased by opening the adjustable motor pulley.
11. Any increase in speed represents a substantial
increase in the horsepower required by the unit.
12. Motor amperage should always be checked to avoid
serious damage to the motor when speed is varied.
Operation
1. Before starting up or operating fan, check all
fasteners for tightness. In particular, check the
setscrews in wheel hub (or the tapered bushing and
pulleys if applicable).
2. While in the OFF position or before connecting the
fan to power, turn the fan wheel by hand to be sure
it is not striking the venturi or any obstacle.
3. Start the fan and shut it off immediately to check
rotation of the wheel with directional arrow in the
motor compartment.
4. When the fan is started, observe the operation and
check for any unusual noises.
5. With the system in full operation and all ductwork
attached, measure current input to the motor and
compare with the nameplate rating to determine if
the motor is operating under safe load conditions.
6. Keep inlets and approaches to fan clean and free
from obstruction.
Inspection
Inspection of the fan should be conducted at the
first 30 minute and 24 hour intervals of satisfactory
operation.
30 Minute Interval
Inspect bolts, setscrews and motor mounting bolts.
Adjust and tighten as necessary.
24 Hour Interval
Check all internal components. On RDB unit only,
inspect belt alignment and tension. Adjust and tighten
as necessary.

Routine Maintenance

Figure 12b
IMPORTANT
Adjust (tighten) belt tension after the first 24-48 hours
of operation.
DANGER
Disconnect and secure to the "off" position all
electrical power to the fan prior to inspection or
servicing. Failure to comply with this safety precaution
could result in serious injury or death.
Greasing of motors is only intended when fittings are
provided. Many fractional horsepower motors are
permanently lubricated and should not be lubricated
after installation. Motors supplied with grease fittings
should be greased in accordance with manufacturers'
recommendations. Where motor temperatures do not
exceed 104ºF (40ºC), the grease should be replaced
after 2,000 hours of running time as a general rule.
Wheels require very little attention when moving clean
air. Occasionally, oil and dust may accumulate causing
imbalance. When this occurs, the wheel and housing
should be cleaned to ensure smooth and safe operation.
All fasteners should be checked for tightness each time
maintenance checks are performed prior to restarting
unit.
A proper maintenance program will help these units
deliver years of dependable service.
CAUTION
Uneven cleaning of the wheel will produce an out of
balance condition that will cause vibration in the fan.
WARNING
This unit should be made non-functional when
cleaning the wheel or housing (fuses removed,
disconnect locked off).
Roof Mounted Downblast Fans
7

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Rdb

Tabla de contenido