THERMOMETRICAL PROBES DIAGNOSTIC
Errors on probes are indicated as follows:
• FLt relay (FAULT relay) switch off.
• FAULT LED turns on.
• LED of the relative channel blinks and the fault state is stored.
In these case it is possible to know the type of failure:
• PT100 probe interrupted, the blinking word ICF appears on
display together with the number of the channel
• PT100 probe is in short circuit state, the blinking word SCF
appears on display together with the number of the channel.
When the device detects one channel in failure state, it stores the
situation and holds blinking the relative LED.
To clean the failure state in memory keep pushed the AUTO/
MANUAL button until a rES word appears on display.
The air cooling status is shoed as following:
• Led Air off: all cooling are off.
• Led Air on: one cooling system is active.
• Led Air blink: all cooling system are active.