g. remove the cable. insert the new cable following the same route.
h. remove the wooden wedge from behind the unit. lock the cable's three poles in the terminal strip and
tighten the screws. Block the cable with the clamp.
i.
Close the protection of the board.
l.
reassemble the cover of the machine.
m. Refit the two wedged-in covers upper and lower.
This operation must be performed by specialized personnel possessing the requirements indicated
by law.
2.4.7 -

TOP/BOTTOM INSTALLATION CONFIGURATION

This unit may be installed either at the bottom of the wall (adjacent to the floor) or at the top (adjacent to the
ceiling). The air jet can be modified to optimize air distribution and occupant comfort by changing the position
of the air outlet fap.
Figure 31 refers to a unit configured for installation near the floor in which air flows upwards. The same con-
figuration may also be used to install the unit near the ceiling with the cooling function, allowing an increase
to the airflow in the room.
Figure 32 refers to a unit configured for installation near the ceiling in which air flows downwards.
THE FOLLOWING OPERATIONS MUST BE PERFORMED WHEN THE UNIT IS SWITCHED OFF AND
DEENERGIZED.
Changing the configuration (see fig. 31-32):
a. Carefully open the air outlet flap.
b. Unhook the flap (side and central hooks on the baffles).
c.
remove the pin (P1) and turn the fap 18Q°.
d. insert the pin (P1) on the right-hand side of the fap.
e.
insert the fap into the unit by inserting the pin into the top hole on the right-hand side in the opening (P2),
and the flap's left-hand hole on the upper pin that is on the left-hand side in the opening.
After having performed the steps required to change the air outlet flap position it is necessary to configure
the unit's control board by following the instructions listed in chapter 2.5 of this manual.
FOR CORRECT UNIT OPERATION EACH TIME THE CONFIGURATION OF THE AIR OUTLET FLAP
IS MODIFIED THERE MUST BE A CORRESPONDING CHANGE TO THE CONTROL BOARD'S SET-
TINGS.
Prior to starting the unit the two supplementary filters (green purifying filter and black active carbon
filter) contained in the parts bag must be installed. Refer to section 2.6.1, which describes how to
clean the filters, to understand both how to remove and reinstall them.
2.5 - OPERATING TESTS AND ANOMALY DIAGNOSIS (Fig.B)
the unit is able to perform a brief auto-diagnosis cycle to check that the internal components are operating
normally. During process the installer can configure the control board based on whether installation was
applied near the ceiling or near the floor.
to activate the self-diagnosis function, use the following procedure:
Energize the unit and ensure it's on stand-by (no LED should be lit on the console).
Press the reset key positioned underneath the hole to the left side of the console (H) with a pointy object
for at least 10 seconds. the sound emitted indicates the self-diagnosis function has been activated.
USA - 11
MAESTRO SMART