8
Advanced Interface Converter (AIC+) and DeviceNet Interface (DNI)
Wiring
Attaching the RS-485 Connector to the Communication
IMPORTANT
Cable
A daisy-chained network is recommended. We do not recommend
the following:
Attach the connector to the Belden #3106A or #9842 cable as shown below.
Single Cable Connection
Shrink tubing recommended
Blue (#3106A) or Blue with White Stripes (#9842) Drain Wire
Multiple Cable Connection
The table below shows connections for Belden #3106A.
For this Wire/Pair
Shield/Drain
Blue
White/Orange
Publication 1761-IN002B-MU-P - July 2003
4 0 0 7 2 - 0 5 1 - 0 1 _ 1 7 6 1 - i n 0 0 2 b - m u - p . p d 8
Belden #3106A
or #9842
Connector
Connector
INCORRECT
Orange with White Stripes
White with Orange Stripes
to successive device
Connect this Wire
Non-jacketed
Blue
White with Orange Stripe
Orange with White Stripe
Belden #3106A
Belden #3106A
or #9842
or #9842
Connector
6 Termination
5 A
4 B
3 Common
2 Shield
1 Chassis Ground
to previous device
To this Terminal
Terminal 2 – Shield
Terminal 3 – (Common)
Terminal 4 – (Data B)
Terminal 5 – (Data A)
8