1. Safety instructions
1.1 Operating personnel
At the Roclean Injector are only persons alowed who have read and understood these instructions.
In particular, the special safety precautions must be observed strictly.
•
Safety Data Sheets are observed!
•
Safety instruction must be observed on bottles ROCLEAN!
2. Installation and operating
2.1 Rinsing of drinking water pipes and heating circuits
The rinsing of heating circuits occurs in three steps:
First step: mechanical cleaning of the system
Cleaning the system with water - air mixture. The pipes are mechanically clean after the cleaning.
Efficiency losses caused by contamination are eliminated.
Step Two: Chemical cleaning system
By the chemical cleaning potential leavings will flushed clean of impurities from the system. The
chemical cleaning slows a new contamination of the system down and is the basis for a subse-
quent preservation.
Step three: preservation of the system
The chemical forms inside the pipe a protective layer and ensures long-lasting protection of the
system.
Preparation
Mount the Roclean Injector in the flow direction at the water outlet
side at the ROPULS. The GK connector is with ROPULS
connected. The adapter for the bottle is straight down
aligned, then tighten the nut at the GK connection.
Connect the compressed air hose to the air-side pressure
connection.
The water connection on the supply side of the Compressor
must be installed with a sepertator.
They also mount the pressure regulator (solid
Setting: 2 bar) in the flow direction at the water outlet
side at the ROPULS. Check for correct installation (arrow on
regulator in the flow direction) Note:
The use of the regulator is the mechanical cleaning
the system optional, in the subsequent chemical
Cleaning absolutely necessary.
First step - Mechanical cleaning of the system:
ROPULS instructions must be obeyed!
Make sure that the lever „rinse / ROCLEAN" is set to „flush".
Follow the instructions in the manual ROPULS 4.3 „Rinsing with clean installation". Follow steps
1-12 through. Rinse the system as described there. Finally, turn off the flushing compressor off
(pressing the „On / Off" push button) and turn off the water supply.
Second step Chemical cleaning of the system:
1. Mount the pressure reducing valve in the flow direction at the water outlet side at the the
ROPULS (if not already installed, installation see above).
2. Open the ROCLEAN bottle and install at the ROCLEAN - Injector. The bottle without a lid
is screwed into the adapter.
Improper use may leak liquid from the bottle. Avoid contact with it.
If accidental contact happen, read the specific safety instructions.
3. Turn the lever „rinse / ROCLEAN" in position „ROCLEAN".
6
ENGLISH
sideways
compressed air
connection
Installation chemistry
adapter Test
Installation pressure regulator
with flow direction arrow