System Grounding Requirements:
Proper grounding will help to ensure stable
and reliable operation of the DGS-6604. Be
sure to verify that the grounding conditions at
the installation meet the grounding require-
ments and ground all devices appropriately
Ground Connection
Figure 2. Grounding of the DGS-6604
Note:
All grounding conductors should
be connected before the AC power
is applied to the DGS-6604 in-
stalled AC power supplies.
The DGS-6604 with AC power
supplies must be grounded with
a minimum of 0.823 mm2 (or
18AWG) of conductive ground-
ing cable. This cable is connected
between the Equipment Room
Ground and the DGS-6604 Chas-
sis Ground Terminal.
4 u D-Link DGS-6604 Modular Switch

Power Requirements

The power consumption and heat dissipation
figures of the various DGS-6604 components
are listed in the table below:
.
DGS-6600 Series
Module
DGS-6600-CM
DGS-6600-48T
DGS-6600-48S
DGS-6600-48TS
DGS-6600-8XG
DGS-6600 Fan
Tray
DGS-6600 AC
Power Supply
Table 2. Card Power Requirements
Note:
The DGS-6604 provides either
1+1, 2+1, or 3+1 redundant AC
power supplies. D-Link
recommends to use multiple
power supplies for the equipment
to ensure continuous and stable
operation. Redundant power
supplies help to prevent
unexpected power failures.
Redundant power supplies must
be identical.
Maximum
Heat
Power
Dissipation
Consumption
(BTU/Hour)
(W)
54
184
110
375
119
405
114
390
200
684
43
144
854
2913
(@110VAC
(@110VAC
or 220 VAC)
or 220 VAC)