Extra low speed
Minimum Speed
Medium Speed
Maximum Speed
N.B.: in the case of modulating fans, the four symbols mentio-
ned above indicate the interval (extra-low, low, medium
and high) in which the operating speed falls.
N.B.: if the active speed is different from the one selected by
the user (in the case of a forced override), pressing the
button Fan
once will cause the latter to be displa-
yed; pressing again will change this setting.
VALVE
The controller can manage 2- or 3-way valves of the ON/OFF
type (i.e. completely open or completely closed) or modulating
valves (the degree of valve opening may range between 0%
and 100%). As in the case of fans, parameter P14 (confi guration
of analog outputs) must be carefully set based on the type of
valves actually present in the unit, so that the controller will
implement the correct control logic.
1. AIR CONTROL
A. OPENING
The valve opening is controlled according to the operating
setpoint and air temperature setpoint
COOLING
HEATING
B. MODULATING VALVE
The valve opening is controlled according to the operating
setpoint and air temperature setpoint The regulation logic for
opening conforms to the diagrams below.
COOLING
OPENING (%)
Installation and operation manual
10
HEATING WITH 3-SPEED CONFIGURATIONS
HEATING WITH 4-SPEED CONFIGURATIONS
2. WATER CONTROL
The checking of water temperature to enable valve opening
is a function that concerns only confi gurations with 3-way
valves and electrical heater. In such confi gurations the water
temperature will be checked in the following cases:
■ Heating with heat element: operation of the electrical heater
will force the fan to switch on; it is therefore necessary to
prevent excessively cold water from passing through the
unit.
■ Post-ventilation due to switching off of the electrical hea-
ter: this function will be maintained until the set time has
elapsed, even if the operating mode is changed. During
post-ventilation the water temperature enabling signal will
coincide with the one seen for fan operation.
AIR TEMP.
DISPLAY
The active valve indication on the display will be shown by
the symbol
ELECTRICAL HEATER
AIR TEMP.
The electrical electrical heater is a device used to provide
support where necessary in the heating mode.
SELECTION
If provided for in the confi guration, the electrical heater can be
selected in the heating mode by pressing the Sel
ACTIVATION
If use of the electrical heater is selected by the user, it will be
activated on a call from the thermostat based on the room
temperature
AMBIENT TEMP.
N.B.: switching it on will force the fan on as well
OPENING (%)
AMBIENT
TEMP.
OPENING (%)
AMBIENT
TEMP.
WATER
TEMP.
key
AIR TEMP.
FWEC3
Advanced plus electronic controller
FC66002765