Alarm Index and Corrective Action

Table 1 lists each alarm, a possible cause, and a suggested corrective action.
Alarm
PROBE OUT
INVALID HEIGHT
LOW TEMPERATURE
NO TANKS CONFIGURED
MAX PRODUCT
OVERFILL
LOW PRODUCT
HIGH WATER
Table 1. Alarm Index, Cause, and Corrective Action
Cause
Hardware failure - probe
inoperative, or its intercon-
necting wiring to console is
damaged.
Product level too low, caus-
ing the fuel and water floats
to be too close together.
Probe temperature drops
below -4°F (-19.8°C).
No tanks are configured in
Tank Setup.
Product volume increased
beyond preset limit.
Product volume increased
beyond preset limit.
Product volume decreased
below preset limit.
Water level rose above pre-
set limit.
Call for service following the procedures
established for your site.
Call for delivery.
Probe returns to normal operation after
probe temperature rises above -4°F
(-19.8°C).
Configure at least one tank in Tank Setup.
Stop delivery. Do not allow additional deliv-
ery until product volume decreases below
preset limit.
Stop delivery. Check for spillage.
Call for delivery.
Remove water from tank.
6
Alarm Index and Corrective Action
Action