General Instructions; Preventive Maintenance - Parker Hyperchill ICE015 Manual De Uso

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

English
5
Maintenance
a) The machine is designed and built to guarantee continuous opera-
tion; however, the life of its components depends on the maintenan-
ce performed.
b) When requesting assistance or spare parts, identify the machine
(model and serial number) by reading the dataplate located on the
unit.
c) Circuits containing 3 kg or more of refrigerant fl uid are checked to
identify leaks at least once a year.
Circuits containing 30 kg or more of refrigerant fl uid are checked to
identify leaks at least once every six months. ((EU) No. 517/2014 art.
4.3.a, 4.3.b).
d) For machines containing 3 kg or more of refrigerant fl uid, the ope-
rator must keep a record stating the quantity and type of refrigerant
used, an quantities added and that recovered during maintenance
operations, repairs and fi nal disposal ((EU) No. 517/2014 art. 6). An
example of this record sheet can be downloaded from the site: www.
polewr.com.

5.1 General instructions

!
Before performing any maintenance, make sure the power to the
refrigerator is disconnected.
Y
Always use the Manufacturer's original spare parts: otherwise the
Manufacturer is relieved of all liability regarding machine malfunctio-
ning.
Y
In case of refrigerant leakage, contact qualifi ed and authorized
personnel.
Y
The Schrader valve must only be used in case of machine malfun-
ction: otherwise any damage caused by incorrect refrigerant charging
will not be covered by the warranty.
ICE015-057

5.2 Preventive maintenance

To guarantee lasting maximum chiller effi ciency and reliability, carry out:
Z
every 6 months - clean the condenser fi ns and make sure com-
pressor electrical absorption is within the dataplate values;
Z
Maintenance (par.7.5)
a) kit for maintenance;
b) service kit;
c) individual spare parts.
5.3 Refrigerant
Z
Charging: any damage caused by incorrect charging carried out
by unauthorized personnel will not be covered by the warranty.
Y
The equipment contains fl uorinated greenhouse gases.
At normal temperature and pressure, the R407C refrigerant is a co-
lourless gas classifi ed in SAFETY GROUP A1 - EN378 (group 2 fl uid
according to Directive PED 2014/68/EU);
GWP (Global Warming Potential) = 1774.
!
In case of refrigerant leakage, air the room.
5.4 Dismantling
The refrigerant and the lubricating oil contained in the circuit must be
recovered in conformity with current local environmental regulations.
The refrigerant fl uid is recovered before fi nal scrapping of the
equipment ((EU) No. 517/2014 art.8).
%
frame and panels
steel/epoxy resin polyester
tank
aluminium/copper/steel
pipes/collectors
copper/aluminium/carbon steel
pipe insulation
NBR rubber
compressor
steel/copper/aluminium/oil
condensator
steel/copper/aluminium
pump
steel/cast iron/brass
fan
aluminium
refrigerant
R407C (HFC)
valve
brass/copper
electrical cable
copper/PVC
6/8
Recycling
Disposal