4.
Wire the detector (see Figures 3 and 7).
UL/cUL installations:
to National Electrical Code, NFPA70, and CSA C22.1,
Canadian Electrical Code Part I, Safety Standards for
electrical Installations.
5.
Select the desired jumper and DIP switch settings (see
Figure 5). See "Jumper settings" below for more
information.
6.
Remove the blinders and add the stickers, if required. See
"Configuring the coverage pattern" on page 5 for more
details.
7.
For ceiling-mount applications that require a 90° coverage,
use the SB01 swivel-mount bracket.
Note:
Using the swivel-mount bracket has not been
evaluated by UL/cUL. Ceiling mount application has not
been evaluated by UL/cUL.
8.
Close the cover.
9.
Insert the screw and place the custom insert.
For EN 50131 Grade 3 installations, do not use mounting
position C (only applicable for AM detectors).
Jumper settings
See Figure 5 for the jumper locations in the detector.
J1: Mode jumper (only available on EV1012AM models)
On: BI-curtain mode (default). In this mode an extra level of
processing is applied to provide enhanced stability in the
presence of false alarm hazards. Bi-curtain is used to reduce
the possibility of false alarms. It looks for signal verification and
requires the intruder to be seen in two curtains
This mode is not suitable for single curtain applications.
Off: Standard mode, suitable for most of the wide angle and
single curtain applications.
J2: PIR enabling the LED
On: Enables the detector LED at all times (default).
Off: Puts the LED under control of the WT (walktest) input. If
the WT input is connected to GND (terminal 1), the red LED
goes on for 3 seconds when a PIR intruder alarm is detected.
If the WT input is connected to +12 V (terminal 2) or floating,
the red LED is disabled.
J3 and J4: Dual loop setting
This sets the alarm and tamper relays. It allows you to connect
the detector to any control panel. Use jumpers 3 and 4. See
Figure 7.
J5: D/N mode (Day/Night) or Rtest (remote test) setting
Use this jumper to set terminal 8 to either D/N or Rtest. UTC
Fire & Security recommends that you use D/N to manage the
AM/TF activation when required. Use Rtest to test the detector
from the control panel. The detector will activate the Alarm
relay if the test result is positive, and the AM relay if the test
result is negative.
On: Terminal 8 = D/N (default).
Off: Terminal 8 = Remote test.
4 / 36
All wiring must be made according
J6: Polarity setting of the control voltage (CV)
On (factory default):
•
The detector is in Day mode (system disarmed) when the
D/N input is connected to GND (terminal 1)
•
The detector is in Night mode (system armed) when the
D/N input is connected to +12 V (terminal 2)
•
The detector is in Walk Test Off mode (LEDs are disabled)
when the WT input is connected to GND (terminal 1)
•
The detector is on Walk Test On mode (LEDs are
enabled) when the WT input is connected to +12 V
(terminal 2)
Off:
•
The detector is in Day mode (system disarmed) when the
D/N input is connected to +12 V (screw terminal 2).
•
The detector is in Night mode (system armed) when the
D/N input is connected to GND (terminal 1).
•
The detector is in Walk Test Off mode (LEDs are disabled)
when the WT input is connected to +12 V (terminal 2).
•
The detector is on Walk Test On mode (LEDs are
enabled) when the WT input is connected to GND
(terminal 1).
D/N and WT functionality
The D/N input:
•
Controls the LED functionality together with the WT input.
•
Resets the alarm memory
•
Controls the AM relay functionality during the NIGHT
mode together with SW1.
The WT input controls the LED functionality together with the
D/N input.
When the detector is in the Day mode and Walk Test On
mode, the LEDs of the detector can be activated. See "LED
indication" on page 5 for more information.
During the Night mode the LEDs are always switched off.
If a PIR intruder alarm if detected in the Night mode and the
detector switches back to Day mode, the red LED starts
flashing to indicate an alarm in memory.
The alarm memory is reset by switching the detector to Night
mode.
DIP switch setting
SW 1: When to signal AM (anti-masking) or TF (technical
fault) output
On: Signals AM or TF only when the system is in Day mode
(default). Note that SW 5 must be in the OFF position for this
functionality to be enabled.
Off: Always signals AM or TF during Day and Night mode.
SW 2: AM sensitivity
On: Selects a higher level of AM sensitivity. AM relay reacts
within 6 seconds.
Off: Selects the standard AM sensitivity. AM relay reacts within
12 seconds (default).
SW 3: Resetting the AM/TF output
The system will only reset an AM alarm if it has ensured that
the cause of the AM alarm has been removed. If the AM
P/N 146169999-10 • REV C • ISS 02APR12