18 - OPERATION DEFECTS
This paragraph shows some possible operation defects, along
with their cause and applicable remedy.
MAINS led does not switch on
It means that there is no voltage on PD16 control unit card.
1. Before acting on the control unit, disconnect through the
disconnecting switch on the power line and remove the power
supply terminal.
2. Be sure that there is no voltage break upstream the control
unit.
3. Check whether the fuse is burnt-out, if so replace it with same
value.
OVERLOAD led is on
It means that there is an overload on accessory power supply.
1. Remove the extractable part containing terminals M1 to M12.
OVERLOAD led will switch off.
2. Remove the overload cause.
3. Reinsert the terminal board extractable part and check that
this led is not on again.
Too long pre-blinking
When a Start command is given and the blinker switches on
immediately but the barrier is late in opening, it means that the
setup cycle count down expired and the control unit shows that
service is required.
Error 1
The following writing appears on display when you exit from
Err1
programming
It means that changed data could not be stored.
This kind of defect has no remedy and the control unit must be
sent to V2 S.p.A. for repair.
Error 2
When a Start command is given and the barrier does not open
and the following writing appears on display
It means that MOSFET test failed.
Before sending the control unit to V2 S.p.A. for repair, be sure
that motors have been properly connected.
Error 3
When a Start command is given and the barrier does not open
and the following writing appears on display
It means that the photocell test failed.
1. Be sure that no obstacle interrupted the photocell beam when
the Start command was given.
2. Be sure that photocells are powered and working; when you
interrupt their beam, you should hear the relay tripping.
Error 5
Once given a start control, the barrier does not open and the
display shows
It means that the test of the safety edges failed.
Check that the menu of the test of safety edges (
been set correctly.
Check that the safety edges enabled from the menu are installed.
Error 7
When given a start control the barrier does not open and the
display shows
This indicates an error in the encoders' operation.
There are two possible causes:
1. Once a START command is received: this means that the
2. A few seconds after movement begins: this means that the
Error 8
When executing a self-learning function, one of the following
conditions occurs:
1. the control is refused and the display shows
2. The procedure stops and the displays shows
Error 9
When you are trying to change the control unit setups and the
following writing appears on display
It means that programming was locked by means of the
programming lock key CL1+ (code 161213).
To change the settings it is necessary to insert in the connector of
the ADI interface the same key used to activate the programming
Err2
lock, and unlock the device.
Error 10
When a start command is given, the barrier does not open and
the display shows the message
This means that the ADI module function test failed
Err3
- 60 -
Err5
Err7
encoders have not been initialized. For the encoders to
operate correctly, the self-learning procedure must be
performed.
encoder is NOT correctly operating. Encoder malfunction or
broken connection
It means that the setting of the control unit is not compatible
with the requested function.
In order to carry out self-learning, the Start inputs must be
Strt
enabled in standard mode (
ADI interface must be disabled (
It means that a safety device has tripped.
Er10
Co.tE
) have
Err8
StAn
menu set to
) and the
i.Adi
no
menu set to
).
Err8
Err9