Infosec E3 PERFORMANCE 5000VA Manual De Usuario página 47

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

06: Battery total AH setting
Interface
07: EPO logic setting
Interface
08: Input Waveform Sensitivity setting
Interface
INFOSEC UPS SYSTEM - 15, rue du Moulin - 44880 Sautron - FRANCE - www.infosec-ups.com
Hot Line – Tel + 33 (0)2 40 76 15 82 - Fax + 33 (0)240 94 29 51 - hotline@infosec.fr – 12 18 AA 59 205 19
Setting
Parameter 2: Set up the battery total AH of the UPS.
7-999: setting the battery total capacity from 7-999 in AH.
Please set the correct battery total capacity if external
battery bank is connected.
Setting
Parameter 2: Set up the EPO function control logic.
AO: Active Open (Default). When AO is selected as EPO
logic, it will activate EPO function with Pin 1 and Pin 2 in
open status.
AC: Active Close. When AC is selected as EPO logic, it
will activate EPO function with Pin 1 and Pin 2 in close
status.
Setting
Parameter 2: Set Input Waveform Sensitivity.
St1: Input voltage waveform detection is highly sensitive.
(Default)
St2: Input voltage waveform detection is middle sensitive.
St3: Input voltage waveform detection is low sensitive.
(use with generators or Step wave input)
47

Publicidad

Tabla de contenido

Solución de problemas

loading

Este manual también es adecuado para:

E3 performance 5000 rt iecE3 performance 5000 rt nema hv

Tabla de contenido