Default - Factory Settings; Selecting Default Configuration - "Def - Macurco CM-6 Instrucciones De Utilizacion

Detector, controlador y transductor de monóxido de carbono
Ocultar thumbs Ver también para CM-6:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Macurco CM-6/CM-12 Manual (Rev-1.1) Eng
4.5 Default – Factory Settings
The CM-xx comes pre-programed with these default settings:
Setting:
Power Up Test
Display
Buzzer
Alarm Relay Setting
Alarm Relay Configuration
Fan Relay Setting
Fan Relay Delay
Fan Relay Minimum Runtime
Fan Relay Latching
Trouble Fan Setting
4-20mA
Calibration due
To change settings, remove the Philips screw on the front of the CM-6. Pull off the front cover of the unit.
To reset the device to factory settings, see section 4.5.1 Selecting Default Configuration – "dEF
4.5.1 Selecting Default Configuration – "dEF"
To select the Default Configuration, in normal mode, push the Next button to get to "Con" or the Configuration menu. Then
push the Enter button to enter the Con menu. The first selection is the "dEF" or Default setting. Push Enter. If it is already in
Default configuration, there will be no action. If it is not already in Default configuration, "nO" will be displayed. Push Next to
REV – 1.1
Default:
On
On
On
200 ppm
Normally Open (NO)
35 ppm
3 minutes
0 minutes
Off
Off
bAS (basic)
dIS (disabled)
Figure 4-1 Board View
[34-2900-0511-6]
20 |
P a g e

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Cm-12

Tabla de contenido