Macurco CM-6/CM-12 Manual (Rev-1.1) Eng
change it to "YES" (flashing) then push Enter to confirm the change (solid) and push Enter again to return to "dEF" in the con
menu. Push Next until "End" is displayed then push Enter to get back to normal operation.
Note: This menu cannot be changed when CM-XX is in calibration due or calibration overdue. (Refer to Section
4.5.13
Calibration Period Settings – "CAL"
for information on calibration due and calibration overdue.)
4.5.2 Power-Up Test Setting – "PUt"
To select the Power Up Test Configuration, in normal mode, push the Next button to get to "Con" or the Configuration menu.
Then push the Enter button to enter the Con menu. Then push the Next button to get to the second selection "PUt" or Power
Up Test setting. Push Enter. If the testis "On" push Next to turn it "OFF" (flashing) then push Enter to confirm the change (solid)
and push Enter again to return to "PUt" in the Con menu. Push Next until "End" is displayed then push Enter to get back to
normal operation.
4.5.3 Display Setting – "dSP"
To select the Display Configuration, in normal mode, push the Next button to get to "Con" or the Configuration menu. Then
push the Enter button to enter the Con menu. Then push the Next button to get to the third selection "dSP" or Display setting.
Push Enter. If the display is "On" push Next to turn it "OFF" (flashing) then push Enter to confirm the change (solid) and push
Enter again to return to "dSP" in the Con menu. Push Next until "End" is displayed then push Enter to get back to normal
operation.
4.5.4 Buzzer Setting – "bUZ"
To select the Buzzer Configuration, in normal mode, push the Next button to get to "Con" or the Configuration menu. Then push
the Enter button to enter the Con menu. The forth selection is the "bUZ" or Buzzer setting. Push Next twice to get to "bUZ" then
Enter. If the display is "On" push Next to turn it "OFF" (flashing) then push Enter to confirm the change (solid) and push Enter
again to return to "bUZ" in the Con menu. Push Next until "End" is displayed then push Enter to get back to normal operation.
4.5.5 Alarm Relay Setting – "ArS"
To select the Alarm Relay Setting, in normal mode, push the Next button to get to "Con" or the Configuration menu. Then push
the Enter button to enter the Con menu. The fifth selection is the "ArS" or Alarm Relay Setting. Push Next three times to get to
"ArS" then Enter. If the display is "dIS" (disabled) push Next to change it to 50, 100, 150 or 200 ppm (flashing) then push Enter
to confirm the change (solid) and push Enter again to return to "ArS" in the Con menu. Push Next until "End" is displayed then
push Enter to get back to normal operation.
4.5.6 Alarm Relay Configuration – "Arc"
To select the Alarm Relay Configuration, in normal mode, push the Next button to get to "Con" or the Configuration menu. Then
push the Enter button to enter the Con menu. The sixth selection is the "Arc" or Alarm Relay Configuration. Push Next four
times to get to "Arc" then Enter. If the relay is "nO" (normally open) push Next to turn it to "nC" (flashing) then push Enter to
confirm the change (solid) and push Enter again to return to "Arc" in the Con menu. Push Next until "End" is displayed then
push Enter to get back to normal operation.
4.5.7 Fan Relay Setting – "FrS"
To select the Fan Relay setting, in normal mode, push the Next button to get to "Con" or the Configuration menu. Then push the
Enter button to enter the Con menu. The seventh selection is the "FrS" or Fan Relay setting. Push Next five times to get to "FrS"
then Enter. If the fan relay is "dIS" (disabled) push Next to change it to 15, 25, 35, 50 or 100 ppm (flashing) then push Enter to
confirm the change (solid) and push Enter again to return to "FrS" in the Con menu. Push Next until "End" is displayed then
push Enter to get back to normal operation.
21 |
REV – 1.1
[34-2900-0511-6]
P a g e