Fault Finding - Tonon CA'D'ORO Serie Installación Uso Y Mantenimiento

Ventilconvectores
Tabla de contenido

Publicidad

5.0 MASTER KEYBOARD CONTROL OF
AN AREA OF FAN COIL HEATERS
MAX. 15 FAN COIL HEATERS WITH
"CBE" CONTROLS
- Controls the entire network of fan coil
heaters in the area, the settings of the
operating parameters are common to
all;
- Using the local keyboards on board
each heater, if fitted, the settings made
by the MASTER can be changed; a new
setting input by the MASTER cancels the
local settings;
- Each fan coil heater has an "FC100"
electronic board fitted;
- Each fan coil heater requires electric
supply of 230V 50Hz;
- The local keyboards are optional;
- The fan coil heaters must be connected
to each other by a screened lead (2 x 0.5
2
mm
) with a maximum length of 30 m.
6.0 START UP
Control that the cover and filter are
c o r r e c t l y a s s e m b l e d a n d t h a t t h e
electric connections have been made in
conformity with the enclosed diagrams.
T u r n t h e h e a t e r o n a n d c h e c k t h e
controls to ensure the fan-coil heater
and accessories work properly.
1 - S u m m e r - w i n t e r - o f f s e l e c t i o n
switch.
2 - Fan regulation.
3 - Room temperature regulation
(VTP/AB versions).
1
2
AIR CONDITIONING
HEATING
7.0 REGULATION ACCESSORIES
Ensure that the accessories have been
c o r r e c t l y a s s e m b l e d a n d t h a t t h e
electric connections have been made as
given in the instructions included with
the kit.
8 . 0 U S I N G T H E F A N - C O I L
HEATER
Ensure that the air-intake zone is free
a n d t h e r e i s n o t h i n g c o v e r i n g t h e
d e l i v e r y g r i d ( d o n o t u s e i t t o d r y
washing, or place anything on top of it)
otherwise the heater will not work
correctly.
9.0 MAINTENANCE
Correct periodic maintenance means
1
MASTER KEYBOARD
Electronic card configuration
DIP SWITCH
DIP SWITCH
ON
ON
OFF
OFF
1 2 3 4
1 2 3 4
MASTER
SLAVE
safe top quality performance.
B e f o r e b e g i n n i n g a n y s o r t o f
maintenance:
- Turn the power off to the fan-coil
heater
- Ensure that the solenoid or holder do
not allow water to circulate in the
exchanger.
- Use protective gloves
Once a month or after heavy use,
clean the filter using a vacuum cleaner
or wash it with neutral detergent. If
the filter is still not clean request a
new one from our service centre.
How to remove the filter (see the
figure):
- Unscrew the fixing screws.
- Pull the filter downwards towards
the floor (or the wall in horizontal
versions).
O n c e a y e a r o r a f t e r a l o n g t i m e
without being used, clean the battery
with a compressed air jet and check
that the condensation outlets are not
blocked.
Do not pour water onto the heater.
The electric motor does not require
maintenance.
If the heater is not used and the outside
temperature falls below 0°C, empty the
exchanger by opening the screws below
3
the bottom attachment and add mono
ethylene glycol to the water to lower
t h e f r e e z i n g t e m p e r a t u r e t o t h e
required level.
* R E A D T H E I N S T R U C T I O N
M A N U A L C A R E F U L L Y B E F O R E
M A K I N G A N Y S E T T I N G S O R
C A R R Y I N G O U T T H E
MAINTENANCE WORK.
* I F T H E F A N - C O I L H E A T E R I S
DISSEMBLED AND REASSEMBLED
THE INSTRUCTION MANUAL MUST
BE SCRUPULOUSLY FOLLOWED.
* P A Y S P E C I A L A T T E N T I O N T O
HOW THE HEATER IS USED WHERE
"ATTENTION" OR "DANGER" ARE
WRITTEN, TO AVOID DAMAGE TO
T H E H E A T E R , P E O P L E A N D
PROPERTY.
* T O N O N S . P . A . D E C L I N E S A L L
RESPONSIBILITY FOR DAMAGED
CAUSED BY INCORRECT USE OF
THE FAN-COIL HEATER AND BY
F A I L U R E T O F O L L O W T H E
I N S T R U C T I O N S G I V E N I N T H I S
2
3
Fan coil heater no. 1
Electronic card
Master configuration
A
A
DIP 1 2 3 1 2 3 1 2 3 4 1 2 3 4
12 V AC
230 V
TRANSF.
2
Screened lead (2 x 0.5 mm
) max. length 30 m.
24 25 26
Master
keyboard
A : Local keyboard is optional
MANUAL.

10.0 FAULT FINDING

FAULT
No air comes out
Little air comes out
Poor heating/cooling
* FOR ANY PROBLEMS THAT ARE
N O T C O V E R E D B Y T H E
INSTRUCTION MANUAL, CONTACT
T H E T O N O N S . P . A . S E R V I C E
CENTRE.
* ATTENTION
In case of fire water must not be used –
only powder or CO
extinguishers.
2
* SPARE PARTS
Use only original spare parts.
* WARRANTY
T h e w a r r a n t y i s v a l i d f o r 3 y e a r s
(except the electric parts which are
covered for 1 year).
The warranty is valid from the date the
17
4
Fan coil heater no. 2
Fan coil heater no. 3
Electronic card
Slave configuration
Slave configuration
A
DIP 1 2 3 1 2 3 1 2 3 4 1 2 3 4
DIP 1 2 3 1 2 3 1 2 3 4 1 2 3 4
12 V AC
230 V
TRANSF.
CAUSE
The motor does not turn
Check the power supply
The consent thermostat
Increase the intake water
does not close
temperature
Blocked filter or battery
Clean the filter and battery
Airflow blocked
Unblock the airflow
Air in the hydraulic circuit
Bleed the hydraulic circuit
Little water in the circuit
Check the boiler or cooler
Intake water temperature
Check the boiler or cooler
low/high
heater is installed.
The warranty is no longer valid if
repairs or alterations are made by
unauthorised persons, or due to faults
that are not caused by original faults of
the components or its construction.
Electronic card
12 V AC
230 V
TRANSF.
REMEDY