[116] Periodic reduction
Pressure reduction due to stopped pump.
[117] Periodic reduction interval
Time to stop pump at zero flow rate.
[118] Pump exclusion delay
Exclusion delay in seconds of the pumps
after the first.
[119] Pump switch-on delay
Switch-on delay in seconds of the
pumps after the first.
IF MOTORS OVER 24A DEFAULT 10
[120] Minimum H2O Pressure
Pressure value to be set according to
the pressure of the column of water on
delivery.
[121] Restarting pressure
Pressure at which the inverter restarts.
IF MOTORS OVER 24A DEFAULT 0.5
[122] Danger pressure
Set
percentage
of
pressure beyond which the control unit
goes into excess pressure alarm status.
[123] Pump rotation interval
Time of daily change in the pump
starting order.
0h: No change.
1-24h: Change according to the set time.
25h: Change at each restart or by
remote control.
26h: Change every 26 seconds to test
the systems (TEST OPTION TO BE
USED
ONLY
COMMISSIONING
SERVICING)
[124,
125
and
126]
Interval for Pump 1, 2 and 3
Total running hours to be reached before
performing maintenance on Pump P1,
P2 and P3.
Field
0.0 – 2.0 bar
000 – 100 s
000 – 100 s
000 – 100 s
0.0 – 5.0 bar
0.0 – 2.0 bar
the
maximum
0 – 150 %
0 – 25 h
DURING
AND/OR
Maintenance
0 - 99999 h
ENGLISH
Default
See parameter 101
0.5 bar
030 s
002 s
002 s
(10 s)
0.5 bar
0.3 bar
(0.5 bar)
80 %
25 h
10000 h
94
BOOSTER
CIRCULATORS
See parameter 101
NOT PRESENT
NOT PRESENT
NOT PRESENT
NOT PRESENT
NOT PRESENT
NOT PRESENT
NOT PRESENT