Operation
2.8 COLD WEATHER OPERATION/DE-ICER
Under certain weather conditions (temperatures below 40° F (4°
C) and a high dew point), the engine may experience icing of the
carburetor and/or the crankcase breather system. To eliminate
this problem, this generator engine is fitted with a winter/summer
valve. This directs hot air into the carburetor during cold weather
operation. Always make sure the winter/summer valve is in the
correct location relative to the weather conditions.
Figure 9 – Winter/Summer Valve
2.9 TO START THE ENGINE
Never start or stop engine with electrical devices plugged into
the receptacles AND devices turned on.
• Unplug all electrical loads from the unit's receptacles before
starting the engine.
• Make sure the unit is in a level position.
• Open the fuel shut-off valve (Figure 10).
• Pull engine CHOKE knob outward to "Full Choke" position
(Figure 11).
Figure 10 – Fuel Shut-off Valve
10
Figure 11 – Choke Operation
If engine fires but does not continue to run, ensure choke
knob is in the "Full Choke" position and repeat starting
instructions.
2.10 HIGH ALTITUDE OPERATION
The fuel system on this generator may be influenced by operation
at high altitudes. Proper operation can be ensured by installing an
altitude kit when required. See the table below to determine when
an altitude kit is required. Operating this generator without the
proper altitude kit installed may increase the engine's emissions
and decrease fuel economy and performance. Kits may be
obtained from any Dealer, and should be installed by a qualified
individual.
Unit
Altitued Range*
0 - 2000 ft
10 kW
2000 - 6500 ft**
* Elevation above sea level
** At elevations above 6500 ft, the engine may experience
decreased performance.
• Press and hold the Start/Run/Stop switch in the "Start"
position. The engine will crank and attempt to start. When the
engine starts, release the switch to the run position.
• When the engine starts, push choke knob to "1/2 Choke"
position until the engine runs smoothly and then fully in to the
"Run" position. If engine falters, pull choke knob back out to
"1/2 Choke" position until the engine runs smoothly and then
to "Run" position.
2.11 STOPPING THE ENGINE
• Shut off all loads, then unplug the electrical loads from
generator panel receptacles. Never start or stop the engine with
electrical devices plugged in and turned on.
• Let engine run at no-load for several minutes to stabilize the
internal temperatures of engine and generator.
• Move Start/Run/Stop or On/Off switch to the "Off" position.
• Close fuel valve.
NOTE:
Kit Part Number
Not Required
0J3797