Gorgy Timing RADIO TIMING GTC Manual De Utilización página 38

Reloj patrón y programador
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Power supply
230V AC +15% -15% / 50-60Hz.or 115V
Power consumption 45 VA.
Power supply fitted with mains filter and fuse.
Display
LCD display of 80 characters (4 rows)
Character height 3,5 mm.
time base
CMOS-technology 80C51 low-power microcontroller.
Quartz 32,768 KHz with a drift of 0.1 sec in 24 hrs between 20° C and 30° C.
time keeping by quartz time base > 10 years, provided by a lithium battery.
Programming unit
3 independent relays, voltage-free output, breaking capacity 250 volts 10 A.
1 pre-wired 230-volt output relay,10A breaking capacity.
128 program steps for each relay.
Relays are programmable in on-off mode or in timeout mode
(From 1 up to 59 seconds).
Daily and annual programming for holidays and public holidays.
128 days available for holidays.
Program backup via lithium battery > 10 years.
time pulse distribution
The Radio Timing GTC exists in two pulse distribution versions.
One-minute version, parallel, 24V inverted 1A, pulse duration 1 second, protection
against short-circuits.
Half-minute version, serial, inverted, on-line current adjustable via potentiometer
(40-140mA), available voltage 48 volts, open-line detection.
Backup in case of main failure achieved via pulse state memorization
aFnOR nFS 87500 time code distribution
The Radio Timing GTC may optionally be equipped with an AFNOR NFS 87500 time-
code output, carrier frequency 1Khz.
Galvanic insulation by transformer. Output level 2.2 Vcc. Output impedance 10 Ohms
Ability to drive 50-250 clocks via 5/10th bifilar link.
aScII code distribution (refer to option: InPUt or OUtPUt aScII RS 232/ RS422-485)
38
by lithium battery > 10 years.
MDE-Radio-Timing-GTC-3080V2.3