System Connectors

Low Voltage connections to signal fault contacts, transfer switch communication and auxiliary 12VDC power are made via a
field connection terminal block in control board area. Compare this illustration with your generator to familiarize yourself
with the location of these connections.
A - Two Pin Terminal Block — Used to connect utility
240 VAC from fuse block in ATS to the control board.
Connect only one wire per terminal.
B - Fault Contacts — Use NO, COM and NC to hook up a
siren, light, etc. to alert you in case of a fault. Contacts
reverse state (NO goes to NC and vice versa) upon a
fault condition.
C - Transfer Switch Communication (TxRx and TxRx
GND) — Connect to transfer switch control board for
communication interface using 18AWG twisted pair
wire.
• For power output connection (Line 1, Line 2, Neutral, and Ground), 300V, 6 AWG copper wire, or 300V, 4 AWG aluminum wire, (ref.
NEC Table 310.16, 100 ft. Use National Electric Code for correction factors and wire size calculations).
• For utility circuit connection (Utility A and Utility B) use #14 AWG minimum copper 300 volt 90°C wire or 300V, 4 AWG aluminum wire.
• For transfer switch communication use #18 AWG twisted pair conductors, no greater than 200 ft in length, 300 volt 90°C wire.
• When connecting to the terminal block, fasten only one wire to each connector screw.
• Torque terminal block screws to 4.4 in-lb (0.49 Newton meter).
• Torque circuit breaker connections to 45 in-lb (5 Newton meter).
A
]
NEUTRAL
G
GROUND
]
LINE 1
F
LINE 2
E
D - +LED and GND Connection — Not required for wireless
E - Eight Pin Terminal Block — Used to connect signal
F - Power Connection (Line 1 and Line 2) — Power
G - Neutral and Ground Connection — Connect to transfer
UTILITY A
UTILITY B
NO
COMM
NC
TxRx
TxRx GND
+LED
GND
N/C
monitor included with unit. Available for optional
hardwired remote system status panel accessory,
#6154.
wires to the control board. Connect only one wire per
terminal.
connection to transfer switch.
switch neutral and ground
]
B
]
C
]
D
23