3-11.Warning Code

Warning code
Warning event
01
Battery unconnected
02
IP Neutral loss
04
IP phase abnormal
05
Bypass phase abnormal
07
Over charge
08
Low battery
09
Overload
0A
Fan failure
0B
EPO enable
0D
Over temperature
0E
Charger failure
* These alarms are only for the single input unit.

4. Trouble Shooting

If the UPS system does not operate correctly, please solve the problem by using the table below.
Symptom
No indication and alarm in the front
display panel even though the mains is
normal.
The icon
and the warning code
flash on LCD display and alarm
beeps every second.
The icon
and
LCD display and alarm beeps every
second.
The icon
and
LCD display and alarm beeps twice
every second.
Fault code is shown as 43. The icon
lights on LCD display and
alarm beeps continuously.
Fault code is shown as 14, the icon
lights on LCD display, and
alarm beeps continuously.
Warning code
Possible cause
The AC input power is not
connected well.
EPO function is activated. At
this time, the EPO switch is in
"OFF" status or the jumper is
open.
The
external
flash on
battery
is
connected.
UPS is overload.
UPS is overloaded. Devices
connected to the UPS are fed
flash on
directly
by
network via the Bypass.
After repetitive overloads, the
UPS is locked in the Bypass
mode. Connected devices are
fed directly by the mains.
UPS is overload too long and
becomes fault. Then UPS shut
down automatically.
The
UPS
automatically because short
circuit occurs on the UPS
output.
30
Warning event
10
L1 IP fuse broken*
11
L2 IP fuse broken*
12
L3 IP fuse broken*
Line situations are different in parallel
21
system
Bypass situations are different in
22
parallel system
Locked in bypass after overload 3
33
times in 30 minutes
34
Converter current unbalance
35
Battery fuse broken
3A
Cover of maintain switch is open
3C
Utility extremely unbalanced
3D
Bypass unstable
Remedy
Check if input cable firmly
connected to the mains.
Set
the
position to disable the EPO
function.
or
internal
Check
incorrectly
connected well.
Remove excess loads from UPS
output.
Remove excess loads from UPS
the
electrical
output.
Remove excess loads from UPS
output first. Then shut down
the UPS and restart it.
Remove excess loads from UPS
output and restart it.
shut
down
Check output wiring and if
connected devices are in short
circuit status.
circuit
in
closed
if
all
batteries
are