WARNING Exhaust heat/gases could ignite
combustibles or structures resulting in
death, serious injury and/or property
damage. Contact with muffler area could
cause burns resulting in serious injury.
• DO NOT touch hot parts and AVOID hot exhaust gases.
• Allow equipment to cool before touching.
• Exhaust outlet side of weatherproof enclosure must
have at least 5 ft. (1.5 m) minimum clearance from
any structure, shurbs, trees or any kind of vegetation.
• Standby generator weatherproof enclosure must be at
least 5 ft. (1.5 m) from windows, doors, any wall opening,
shrubs or vegetation over 12 inches (30.5 cm) in height.
• Standby generator weatherproof enclosure must
have a minimum of 5 ft. (1.5 m) overhead clearance
from any structure, overhang or trees.
• DO NOT place weatherproof enclosure under a deck
or other type of structure that may confine airflow.
• Use only flexible fuel line provided. Connect
provided fuel line to generator, DO NOT use with or
substitute any other flexible fuel line.
• Smoke detector(s) MUST be installed and
maintained indoors according to the manufacturer's
instructions/recommendations. Carbon monoxide
alarms cannot detect smoke.
• Keep at least minimum distances shown in General
Location Guidelines to insure for proper generator
cooling and maintenance clearances.
• It is a violation of California Public Resource Code,
Section 4442, to use or operate the engine on any
forest-covered, brush-covered, or grass-covered
land unless the exhaust system is equipped with
a spark arrester, as defined in Section 4442,
maintained in effective working order. Other states
or federal jurisdictions may have similar laws.
Contact the original equipment manufacturer,
retailer, or dealer to obtain a spark arrester designed
for the exhaust system installed on this engine.
• Replacement parts must be the same and installed
in the same position as the original parts.
CAUTION Installing the 15A fuse could cause
the engine to start at any time without warning
resulting in minor or moderate injury.
• Observe that the 15 Amp fuse has been removed
from the control panel for shipping.
• DO NOT install this fuse until all plumbing and wiring
has been completed and inspected.
6
CAUTION Excessively high operating speeds
could result in minor injury and/or equipment
damage.Excessively low speeds impose a heavy
load on generator.
• DO NOT tamper with governed speed. Generator
supplies correct rated frequency and voltage when
running at governed speed.
• DO NOT modify generator in any way.
NOTICE Improper treatment of generator can
damage it and shorten its life.
• Use generator only for intended uses.
• If you have questions about intended use, contact
your authorized dealer.
• Operate generator only on level surfaces.
• Adequate, unobstructed flow of cooling and ventilating
air is critical to correct generator operation.
• The Oil Fill, Oil Drain and the Control Panel doors
must be installed whenever the unit is running.
• DO NOT expose generator to excessive moisture,
dust, dirt, or corrosive vapors.
• Despite the safe design of the generator, operating this
equipment imprudently, neglecting its maintenance or
being careless can cause possible injury or death.
• Remain alert at all times while working on this
equipment. Never work on the equipment when you
are physically or mentally fatigued.
• DO NOT start engine with air cleaner or air cleaner
cover removed.
• DO NOT insert any objects through cooling slots.
• DO NOT use the generator or any of its parts as
a step. Stepping on the unit can cause stress and
break parts. This may result in dangerous operating
conditions from leaking exhaust gases, fuel leakage,
oil leakage, etc.
• If connected devices overheat, turn them off and
disconnect them from generator.
Shut off generator if:
-electrical output is lost;
-equipment sparks, smokes, or emits flames;
-unit vibrates excessively:
-unit makes unusual noises.