Note : All TA models are delivered for two-pipe system (by-pass plug fitted in vacuum gauge port). For one-pipe
system, the by-pass plug must be removed and the return port sealed by steel plug and washer.
IDENTIFICATION
(Not all model combinations are available
Consult your Suntec representative)
TA
2
Pressure range :
30 : 7 - 30 bars
40 : 7 - 40 bars
Preheater
facility
Revision number
General
Mounting
Connection threads
Inlet end return
To nozzle
Pressure gauge port
Vacuum gauge port
Shaft
By-pass plug
Weight
Hydraulic data
Nozzle pressure ranges 30 : 7 - 30 bars
Delivery pressure
setting
Operating viscosity
Oil temperature
Inlet pressure
Return pressure
Rated speed
Starting torque
Choice of heater
Cartridge
Fitting
Rating
PUMP SUNTEC TA TECHNICAL DATA
PUMP
TA : type
Gear set capacity
(see pump capacity curves)
Shaft rotation
(seen from shaft end)
A : clockwise rotation
C : anti clockwise rotation
A
40
10
5
Flange mounting
Cylindrical according to ISO 228/1
G 1/2"
G 1/2"
G 1/4"
G 1/4"
Ø 12 mm
Inserted in vacuum gauge port
for 2 pipe system;
to be removed with a 3/16" Allen key
for 1 pipe system
5,4 kg (TA2)
-
5,7 kg (TA3)
6 kg (TA4)
-
6,4 kg (TA5)
40 : 7 - 40 bars
30 bars
4 - 450 cSt
0 - 140°C max. in the pump
light oil :
0,45 bars max. vacuum to prevent
air separation from oil
heavy oil :
5 bars max.
light oil :
5 bars max.
heavy oil :
5 bars max.
3600 rpm max.
0,3 N.m
Ø 12 mm
according to DIN 40430, NFC 68190 (N°9 elec.)
80-100 W
420010310200 MULTICALOR 300.1-400.1 PR/PR
Olio in aspirazione
Attacco
Olio in pressione
vuotometro o
misura presione
di entrata
Ritorno dell'olio
non utilizzato
al serbatoio o
all'aspirazione
Aspirazione
Grano
di by-pass
inserito
Vite di regolazione
della pressione
Aspirazione
Grano
di by-pass
tolto
INSTALLAZIONE
MONOTUBO
Pump capacity
Capacity (L/h)
1500
1400
TA5
1300
1200
1100
TA4
1000
900
800
TA3
700
600
TA2
500
400
300
200
100
0
0
5
10
15
20
Viscosity =
200 cSt
20 cSt
5 cSt -
Data shown are for new pumps, with no allowance for wear.
23
Attacco
manometro
pressione
Ingranaggio
All'ugello
INSTALLAZIONE
BITUBO
Ritorno
Ritorno
chiuso
2850 rpm
25
30
35
40
Pressure
(bars)
Rated speed = 2850 rpm
EN