Electrical wiring

Full electrical wiring installation must be carried out prior to the installation
of the wind turbine and once the tower has been installed.
Never install the wind turbine if
the regulator and batteries are
not properly connected..
The first step in the electrical configuration is to place the correct battery
bank, with its correct connection configuration and connected according the
manufacturer's specifications, thus obtaining the right voltage and capacity
for the installation to be carried out.
Different types of batteries exist. In the case of domestic hybrid wind energy/
solar energy installations, open lead-acid batteries are recommended and, to
meet the installations charge capacities, certain minimum installation
requirements are essential to assure correct running and durability of the
installation.
The minimum installation recommendations and battery-to-regulator cable
recommendations are the following:
Model
Wind 13+ / 220V
Wind 25.2+ / 220V
Wind 25.3 +/ 220V
CAUTION:
The use of stationary open lead-acid
batteries is recommended.
CAUTION:
Battery Cable
WARNING:
Never invert polarity.
Use appropriate sized cables.
2
10 mm
2
16 mm
2
16 mm
Use of the wrong battery can
cause irreparable damage to
your wind turbine.
Minimum Battery
150 Ah C
100
250 Ah C
100
550 Ah C
100
WARNING:
35