Installation
Auxiliary contact (optional)
1
1
3
Auxiliary contacts OA1G10 and OA3G01 (optional)
Install the auxiliary contacts to the safety switch mechanism
according to the pictures. In the picture 3 the mounting example
is for 200A and 400 A safety switches. In 600 A safety switches,
please, leave the mechanism cover off, when the maximum
amount of auxiliary contacts (3 or 4 pcs) is used. See chapter
Cabling.
Wire size: 1 - 2 × 18 - 14 AWG, 1 - 2 × 0.75 - 25 mm
Torque: 7 lbs.in, 0.78 Nm
200 A, 400 A
0
1
0
Test
0
Main contact
Test contact
(NO)
Test indication
contact (NO)
Test contact
(NC)
Test indication
contact (NC)
1/14 Installation | Instruction Bulletin EOH364/5/6JK/RK/S/SS, 1SCC340032M1401 / A