WARNING: Test all gas piping
and connections for leaks after
installing or servicing. Correct
all leaks at once.
1. Disconnect heater with its appliance main
gas valve (control valve) and equipment
shutoff valve from gas supply piping sys-
tem. Pressures in excess of 1/2 PSIG will
damage heater regulator.
2. Cap off open end of gas pipe where equip-
ment shutoff valve was connected.
3. Pressurize supply piping system by either
opening propane/LP supply tank valve
for propane/LP gas or opening main gas
Test Pressures Equal To or Less Than 1/2 PSIG (3.5 kPa)
1. Close equipment shutoff valve (see Fig-
ure 16).
2. Pressurize supply piping system by either
opening propane/LP supply tank valve
for propane/LP gas or opening main gas
valve located on or near gas meter for
natural gas or using compressed air.
3. Check all joints from gas meter (natural
gas installations, see Figure 17) or from
propane/LP tank (propane/LP gas installa-
tions, see Figure 18) to equipment shutoff
valve. Apply a noncorrosive leak detection
fluid to all joints. If bubbles form, there is
a leak.
4. Correct all leaks at once.
Equipment
Shutoff Valve
Figure 16 - Equipment Shutoff Valve
200033-01B
INSTALLATION
CHECKING GAS CONNECTIONS
Pressure Testing Gas Supply Piping System
Test Pressures In Excess Of 1/2 PSIG (3.5 kPa)
Open
Closed
www.usaprocom.com
WARNING: Never use an
open flame to check for a leak.
Apply a mixture of liquid soap
and water to all joints. If bubbles
form, there is a leak. Correct all
leaks at once.
valve located on or near gas meter for
natural gas or using compressed air.
4. Check all joints of gas supply piping sys-
tem. Apply a noncorrosive leak detection
fluid to all joints. If bubbles form, there may
be a leak.
5. Correct all leaks at once.
6. Reconnect heater and equipment shutoff
valve to gas supply. Check reconnected
fittings for leaks.
Gas Meter
Figure 17 - Natural Gas Supply
Propane/LP
Supply Tank
LP REGULATOR INSTALL 2
Figure 18 - Propane/LP Fuel Supply
Gas Valve
Equipment
Shutoff Valve
Gas Valve
Equipment
Shutoff Valve