Honeywell L7224U Manual Del Usaurio página 10

Ocultar thumbs Ver también para L7224U:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

L7224U OIL AND ELECTRIC BOILER ELECTRONIC AQUASTAT
Aquastat
Error
Code
Err1
Aquastat sensor fault; check water sensor.
Err2
ECOM fault; check EnviraCOM™ wiring.
Err3
Excessive electrical noise or frequency out of range. Hardware fault; replace controller.
Err4
B1 fault; check B1 wiring/voltage.
Err5
Low Line; check L1-L2, 110 Vac.
Warning: Fuse; check ECOM wires, replace fuse.
a
Err6
Err7
Warning: EEPROM, HL, LL, Hdf, Ldf; reset to default values.
b
Repeated B1 fault (voltage present at B1 when output is turned off); check B1
Err 8
wiring/voltage.
a
Warning: Outdoor Reset System failure; communication to Outdoor Reset Module lost,
Err9
Outdoor Reset Module failure, multiple outdoor temperature sensors detected on the
bus, or outdoor temperature sensor failure. Check EnviraCOM wiring (1, 2, 3), check
sensor wiring.
a
Warning: Boost Failure; Boost Mode active at least once per cycle for the last 60
Err 10
consecutive cycles. Check Outdoor Reset curve settings.
a
DHW Module/Sensor failure; communication to DHW Module lost, DHW Module failure,
Err 11
or temperature sensor failure. Check EnviraCOM wiring (1, 2, 3), check sensor wiring.
a
Warnings are generated to enunciate the system is not operating optimally, but the Aquastat is still operating
and maintaining boiler temperature. In the instance where an Outdoor Reset Module is used, the warnings
may indicate a reset curve setting error one or more features is not running optimally, and the Aquastat is
reverting to default settings or has stopped running the Outdoor Reset algorithms. The warnings are cleared
when the issue(s) is resolved.
b
To clear Err 8 condition, depress and hold all three user keys simultaneously for 60 seconds. Err 8 condition
clears and display returns to normal. Err 8 condition is designed to catch welded relays on the Aquastat and
will normally only occur near end of life for the control. If Err 8 condition has occurred early in the controls life,
be sure to check for voltage feedback to B1 when B1 should be off and check current draw on b terminal to be
sure burner is not drawing excessive current. Err 8 condition will keep repeating if B1 fault is not cleared.
69-1720EFS—11
®
CONTROLLER
Table 9. LED Error Codes.
Cause/Action
10
EnviraCO
M Alarm
18
18
18, 58
64
59
92
N/A
25
50, 53, 149
150
146, 147,
148

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Aquastat l7224u

Tabla de contenido