Select The Best Location; Installation Diagram; Install The Outdoor Unit - Panasonic UX09 E5 Serie Manual De Instalación

Unidad exterior de bomba de calor de aire a agua
Ocultar thumbs Ver también para UX09 E5 Serie:

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 7
1

SELECT THE BEST LOCATION

If an awning is built over the unit to prevent direct sunlight or rain, be careful that heat radiation from the condenser is not obstructed.
Avoid installations in areas where the ambient temperature may drop below -20°C for UD models and -28°C for UX models.
Keep the spaces indicated by arrows from wall, ceiling, fence or other obstacles.
Do not place any obstacles which may cause a short circuit of the discharged air.
If outdoor unit installed near sea, region with high content of sulphur or oily location (e.g. machinary oil, etc.), it lifespan maybe shorten.
When installing the product in a place where it will be affected by typhoon or strong wind such as wind blowing between
buildings, including the rooftop of a building and a place where there is no building in surroundings, fi x the product with an
overturn prevention wire, etc. (Overturn prevention fi tting model number: K-KYZP15C)
If piping length is over 10 m, additional refrigerant should be added as shown in the table.
Model
UX09*E5*, UX12*E5*, UD12*E5*,
UD16*E5*, UX09*E8*, UX12*E8*,
UX16*E8*, UD09*E8*, UD12*E8*,
UD16*E8*
Example:
If piping length is 30m, the quantity of additional refrigerant should be 1000g. [(30-10)m x 50 g/m = 1000g]
GWP (R410A) = 2088
2

INSTALL THE OUTDOOR UNIT

INSTALLATION DIAGRAM

A
(Anchor pitch)
After selecting the best location, start installation according to Installation Diagram.
1. Fix the unit on concrete or rigid frame fi rmly and horizontally by bolt nut (ø10 mm).
2. When installing at roof, please consider strong wind and earthquake. Please fasten the installation stand fi rmly with bolt or nails.
DISPOSAL OF OUTDOOR UNIT DRAIN WATER
When a Drain elbow 1 is used, please ensure to follow below:
- the unit should be placed on a stand which is taller than 50 mm.
- cover the ø20mm holes with Rubber cap 2 (refer to illustration below).
- use a tray (Þ eld supply) when necessary to dispose the outdoor unit drain water.
If the unit is used in an area where temperature falls below 0°C for 2 or 3 consecutive days, it is recommended not to use the Drain elbow 1
and Rubber cap 2 , for the drain water freezes and the fan will not rotate.
ACXF60-03260.indb 3
Piping size
Gas
Liquid
Pump Indoor
ø15.88mm (5/8") ø9.52mm (3/8")
It is advisable to avoid more than 2 blockage directions. For better ventilation & multiple-outdoor installation,
please consult authorized dealer/specialist.
This illustration is for explanation purposes only.
Vinyl tape (Wide)
Saddle
Indoor/Outdoor connecting cable
- For UX09*E5*, UX12*E5*, UD12*E5*, UD16*E5* use 4-CORE WIRE
min 4.0mm
2
or 6.0mm
- For UX09*E8*, UX12*E8*, UX16*E8*, UD09*E8*, UD12*E8*,
UD16*E8* use 6-CORE WIRE min 1.5mm
Type designation 60245 IEC 57 or heavier cord
ø9.52mm (3/8") Liquid refrigerant piping
ø15.88mm (5/8") Gas refrigerant piping
[
Check that the cables do not
touch the compressor, etc.
E
UX09*E5*, UX12*E5*, UD12*E5*, UD16*E5*,
UX09*E8*, UX12*E8*, UX16*E8*, UD09*E8*,
UD12*E8*, UD16*E8*
B
2
Rubber ca
p
Rated Length (m)
Max.
For Heat
For
Elevation
Hydromodule
(m)
Unit
+ Tank
7
5
20
2
2
]
Model
620
1
Drain elbow
x 8
Min. Piping
Max. Piping
Additional
Length
Length
Refrigerant
(m)
(m)
(g/m)
3
30
50
A
B
C
D
E
F
140
15
355
450
44
(Unit : mm)
8/25/2016 10:10:06 AM
3