Start/H
max. OFF
ALARMS
motor and Brio Top. If this alarm trips frequently, arrange for the system to be checked by the installer.
To remove the error message from the display immediately, simply press the central key "reset".
contact the installer for assistance. To remove the error message from the display immediately, simply
press the central key "reset".
IT
EN
Maximum starts per hour: sets the maximum start limit in one hour of
the pump. To disable the protection, press the button - until the word
"OFF" appears.
Alarm log "1" : in this screen the user can read the number of alarms that
have tripped due to activation of the dry-running protection (DR) and the
pressure overload device (OP). These data can be checked in the event of a
malfunction.
Alarm log "2" : in this screen the user can read the number of alarms that
have tripped due to activation of the current overload protection (OL) and
the ice protection (IP). These data can be checked in the event of a
malfunction.
Hour counter: this screen displays the total operating hours of Brio Top (in
terms of the time for which the device has been connected to the electric
power supply). If the key "+" is pressed on this page, the number of pump
operating hours is displayed.
Dry running: this message appears when the system is shut down
following absence of water on pump intake. If the auto-reset function is
enabled, Brio Top automatically attempts to restart and check for renewed
availability of water. To remove the error message from the display
immediately, simply press the central key "reset".
Current Overload: this alarm is displayed when electric pump absorption
exceeds the maximum set current as entered in the parameter Imax; this
may occur following intensive use of the electric pump, continuous restarts
at close intervals, problems with the motor windings, seizure of the pump
rotor or following problems with the electrical connection between the
Overpressure: when this alarm trips, this means that Brio Top has
detected a system pressure value over the value set in the parameter
"Plimit". This may occur in applications with the pump under load
conditions, i.e. when the pump pressure is added to the filling pressure on
inlet. If the error occurs frequently, try to increase the parameter Plimit or