GB
2.6
Technical data
2.6.1
Refrigeration data
Designation
Cooling capacity A35 / A35 * / **
Cooling capacity A50 / A35 * / **
Refrigerant type *
Refrigerant quantity *
Temperature setpoint (factory setting)
Fault indication: Switch cabinet interior
temperature (factory setting)
Ambient air temperature
Switch cabinet interior temperature
Air volume flow, exterior circuit
Air volume flow, interior circuit
Condensate separation
2.6.2
Electrical data
Designation
Rated
operating
voltage * / ****
Rated frequency *
Functional range
Power consumption *
Rated current*
Starting current*
2.6.3
Dimensions
Designation
Height DTS
Height DTI
Width
Depth with cover (standard)
Installation depth DTI
Weight
Installation attitude
Unit construction
2.6.4
Other unit data
Designation
Anti-corrosion protection
Protection type
*
Data on the type plate.
***
Max. rated current UL at 60 Hz.
Operating Manual DTS and DTI 6201 / 6301 Multi-Controller (MC) 086100010 © Pfannenberg GmbH
Model DTI/DTS 6201
Q
1000 W
0
Q
780 W
0
Model DTI/DTS 6201
P
el
948 W
A35/A35
I
8,27 A
nom max
I
40 A
Start max
Model DTI/DTS 6201
DTI: 51 kg / DTS: 55 kg
Model DTI/DTS 6201
Standard: Galvanized, electrostatic powder-coated
Variant: Stainless steel cover
When used as intended:
IP 54 against the switch cabinet (EN 60529).
IP 34 against the environment (EN 60529).
**
Use of optional filter mats reduces the cooling capacity.
**** With a change to the rated operating voltage, adapt the
upstream fuse; see
Model DTI/DTS 6301
R 134a
650 g
+35°C (+95°F)
> +50°C (+122°F)
+15°C (+59°F) bis +55°C (+131°F)
+25°C (+77°F) bis +45°C (+113°F)
850 m³/h
850 m³/h
Condensate drain
Model DTI/DTS 6301
115 V
60Hz
DIN IEC 60038
10 A***
10,19 A
Model DTI/DTS 6301
1539 mm
1536 mm
485 mm
218 mm
60 mm
DTI: 54 kg / DTS: 58 kg
Vertical
Standard: Steel sheet
Model DTI/DTS 6301
Adapting the upstream
1500 W
1200 W
1010 W
12,5 A***
42 A
(200°C)
fuse.
Page 13 / 43