GB
2.6
Technical data
2.6.1
Refrigeration data
Cooling capacity at * / **
Refrigerant type *
Refrigerant quantity *
Temperature setpoint (factory setting)
Fault indication: Switch cabinet interior temperature
(factory setting)
Ambient air temperature
Switch cabinet interior temperature
Air volume flow, interior circuit
Condensate separation
2.6.2
Electrical data
Rated operating voltage * / ***
Rated frequency *
Functional range
Rated operating voltage range
Power consumption *
Rated current *
Upstream fuse ***
Cooling capacity at A35/ A20 * / **
Cooling capacity at A35/ A35 * / **
Cooling capacity at A35/ A50 * / **
2.6.3
Dimensions
DTS height
DTI height
Width
Depth with cover (standard) DTS
Depth with cover (standard) DTI
DTI installation depth
Weight
Installation position
Unit construction
2.6.4
Other unit data
Anti-corrosion protection
Protection type
*
Data on the type plate.
***
Max. rated current UL at 60 Hz.
Operating Manual DTS and DTI 6X2E Premium Controller X-Series (XC) 086100099d © Pfannenberg GmbH
Designation
Designation
P
A35 / A35
I
nom max
Designation
Designation
Q
0
+15°C (+59°F) to +55°C (+131°F)
+25°C (+77°F) to +45°C (+113°F)
el
Q
0
Q
0
Q
0
DTI: 84 kg
Standard: Galvanized, electrostatic powder-
coated (200°C)
Variant: Stainless steel cover
When used as intended:
IP 54 against the switch cabinet (EN 60529).
IP 34 against the environment (EN 60529).
**
Use of optional filter mats reduces the cooling capacity.
Model DTI/DTS 6X2E
2000 W – 4500 W
R 134a
1950 g
+35°C (+95°F)
+52°C (+125,6°F)
1430 m³/h
Condensate evaporator
Model DTI/DTS 6X2E
230 V
AC 50 / 60 Hz
DIN IEC 60038
360V – 460V
440 W – 1770 W
12,2 A
16 A
5100 W
4500 W
3700 W
Model DTI/DTS 6X2E
1547 mm
1538 mm
485 mm
372 mm
252 mm
120 mm
DTS: 87 kg
Vertical
Standard: Steel sheet
Model DTI/DTS 6X2E
Page 12 / 42