temperature is only the one set in max. flow temp.
Settings range: 0 % to 20 % / Default: 0%
Menu 7.6.2 Room reference day
The desired room temperature for day mode. As long as this temperature is not
reached, the reference flow temperature is raised or respectiveley lowered according
to the percent setting in "room sensor". If "room sensor" is set to 0%, this function is
deactivated.
Settings range: 10 °C to 30 °C / Default: 20 °C
Menu 7.6.3 Room reference night
The desired room temperature for night mode. As long as this temperature is not
reached, the reference flow temperature is raised or respectiveley lowered according
to the percent setting in "room sensor". If "room sensor" is set to 0%, this function is
deactivated.
Settings range: 10 °C to 30 °C / Default: 20 °C
Menu 7.7 Program selection
Output relay function could control Heating circulation pump see 7.7.1 or Aux. Heat see
7.7.2.
Menu 7.7.1 Heating circulation
Activation of control Heating circulation. See application 1 page 5
Menu 7.7.2 Aux. heat.
Activation of control Aux. heat. See application 2 page 5
MENU LOCK, MENU 8
Menu lock" can be used to secure the controller against
7 Special functions
unintentional changing and compromise of basic
8 Menu lock
functions.
9 Service data
The menus listed below remain completely accessible
▲
▼
OK
despite the menu lock being activated, and can be used
to make adjustments if necessary:
1. Measurement
2. Statistics
3. Times
8. Menu lock
9. Service data
Menu 8.1 Menu Lock Info
To block the other menus, select "Menu lock on".
To enable the menus again, select "Menu lock off".
Setting range: on, off / default setting: off
18
SERVICE DATA, MENU 9
Service data" can be used for remote diagnosis by
a specialist or the manufacturer in the event of an
9.1
90C 2009/05/06 4436
error, etc.
outdoor
0°C
9.2
Flow
0°C
9.3
▲
▼
9.1
9.19
9.2
9.20
9.3
9.21
9.4
9.22
9.5
9.23
9.6
9.24
9.7
9.25
9.8
9.26
9.9
9.27
9.10
9.28
9.11
9.29
9.12
9.30
9.13
9.31
9.14
9.32
9.15
9.33
9.16
9.34
9.17
9.35
9.18
9.36
Subject to technical modifications and amendments. The illustrations and description
are not exhaustive.
Enter the values at the time when the
error occurs into the table.
9.37
9.38
9.39
9.40
9.41
9.42
9.43
9.44
9.45
9.46
9.47
9.48
9.49
9.50
9.51
9.52
9.53