8
TEST RUN
In case of wireless remote controller
Procedure
Remove a small screw which fixes the nameplate of the receiver unit.
1
Remove the nameplate of the sensor section by inserting a minus screwdriver, etc into the notch at the bottom
of the plate, and set the Dip switch to [TEST RUN ON].
Execute a test operation with
•
,
, and
2
• Under status of [TEST RUN ON], the temperature adjustment from the wireless remote controller is invalid.
Do not use this method in the operation other than test operation because the equipment is damaged.
Use either COOL or HEAT operation mode for a test operation.
3
* The outdoor unit does not operate approx. 3 minutes after power-ON and operation stop.
After the test operation finished, stop the air conditioner from the wireless remote controller, and return Dip
4
switch of the receiver section as before.
(A 60-minutes timer clearing function is attached to the receiver section in order to prevent a continuous test
operation.)
LED flash during test operation.
M4 × 25 screw
(2 pieces)
Nameplate
Notch
Small screw
Description
button on the wireless remote controller.
Receiver unit
Spacer
17