Descargar Imprimir esta página

AERMEC VHL 1 Manual Del Usuario página 2

Publicidad

UK
The kit is composed of a valve, the relative actuator and
two gaskets.
The valve is the open or closed type with 1/2" connections,
having single-phase 230 V 50/60 Hz electrical requirements.
The valve can be controlled from command panels (accessori-
es) enabled with the valve control function; before selecting,
consult the characteristics of the command panels.
Control
Shutter stem stroke
Normal position
Power supply voltage
Frequency
Input power during operation
Input current at start-up
Input current during operation
Fluid temperature
Nominal pressure
Max. Differential pressure
Leakage rate
Max. Room temperature
Degree of protection
Diameter of the connections
Connection to connection characteristic
Compatible fluids : water, water mixed with a max. 50% glycol
2
ON-OFF
mm
2,5
By-pass
V
230
Hz
50 - 60
V A
3
A
0,6
A
0,014
°C
2 - 120
PN
16
kPa
150
≤ 0,02%
Kvs %
°C
50
IP
44
Ø DN15 (1/2")
for an even seal
UK
INSTALLATION
WARNING: before performing any maintenance interven-
tion, make sure that the power supply has been cut off.
WARNING: the electric connections, installation of the fan
coils and their accessories must be performed only by persons
possessing the technical and professional qualifications ena-
bling them to perform installation, convert, expand and main-
tain the plants and capable of performing functionality and
safety checks on the plants.
In particular, for the electric connections, the following checks
are needed:
- Electrical system isolation resistance measurement.
- Protective conductors continuity test.
Before installing the VHL 1 kit consult the FCL fan coil installa-
tion manual; it is the installers task to prepare the water and
electrical systems, and to correctly perform the connections with
the unit.
The installation must be performed according to that illustrated
in the given diagrams, using the gaskets supplied with the kit of
the machine.
WARNING! During the installation pay attention to the direc-
tion of flow, before mounting the valve check the mounting
direction by referring to the symbol stamped on the body of the
valve.
The valve body must be installed without excessive torsion,
between 25 and 30 Nm.
Connect the electrical wires of the valve to the terminal strip of
the unit as indicated in the attached wiring diagrams.

Publicidad

loading

Este manual también es adecuado para:

Avhl1uj