Wiring The Ex D Models; 24 Vdc Models - Federal Signal Global Serie Instrucciones De Instalación Y Mantenimiento

Ocultar thumbs Ver también para Global Serie:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

The maximum wire gauge is 2.5 mm
rated 85 °C or higher. Use only stranded cable to terminate the beacon.
The cross-sectional area of the primary earth (ground) must equal the
cross-sectional area of the phase conductor.
Cable termination for these models should be in accordance with
specifications applying to the application. It is recommended that all
cables and cores should be fully identified. Use the appropriate cable
gland for the application. Gland entry threads are M20-1.5 x 6H.
Tools needed:
• 1.5 mm A/F hexagon key
• 2 mm flat-tip screwdriver
• No. 1 Phillips screwdriver
• Wire stripper

Wiring the Ex d Models

To wire the Ex flameproof beacon:
1.
Unscrew the M3 hex set screw on the side of the housing one
full turn.
2.
Remove the lens cover from the housing by turning the
cover counter-clockwise. Three 120 degree spaced reliefs are
provided for a 3/8 in spanner wrench if needed. If the cover
will not unscrew, back out the set screw a few additional turns.
3.
Loosen the captive Phillips screw retaining the printed circuit
board (PCB).
4.
Slide out the PCB until the terminals clear the housing. Strip
the wire insulation 5 mm to 6 mm (0.22 in).

24 Vdc Models

a.
See Figure 10 on page 16. Connect the positive (+) power
source wire to the terminal-block screw marked + .
b. Connect the negative (
block screw marked
Model G-LED Global Series LED Beacon
Installation and Maintenance Instructions
(12 AWG). The wire must be
2
) power source wire to the terminal
.
15

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

G-led led

Tabla de contenido